DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
DVF34, DVF34P
VENTING
INSTALLATION
Continued
UP
UP
Horizontal Venting
Vertical (V)
Horizontal (H)
37" min.
10" max.
Figure 16 - Horizontal Termination Configuration for Rigid Venting
Figure 17 - Horizontal Termination Configuration for Rigid Venting Using One
90
°
Elbow
Horizontal Venting
Vertical (V)
Horizontal (H)
44" min.
29" max.
(30
°
and 90
°
only, no vertical pipe)
55" min.
41" max.
(30
°
elbow, 1' vertical pipe, 90
°
elbow)
67" min.
60" max.
79" min.
84" max.
96" min.
20' max.
Note: This configuration for use with
corner installation.
Horizontal Termination
Configurations
Figures 16 through 19 show different con-
figurations for venting with horizontal ter-
mination. Each figure includes a chart with
vertical minimum/maximum and horizon-
tal maximum dimensions which must be
met. Seal all connections with high tem-
perature silicone sealant (outer pipe only) as
specified in the second warning statement
on page 7. All horizontal terminations re-
quire 1/4" rise per 12" of horizontal run.
FD60
60˚ Starter/
Adapter Required
FD30
30˚ Starter/
Adapter Required