For instructions on draining the cooling jacket, see
Empty the coolant (external cooling)
(page 86).
Supply water flow
For information about dimensioning the water supply for external cooling, please contact your ITT
representative.
External cooling, closed loop
NOTICE: It is extremely important that the cooling water flow is maintained at or above the desired
minimum level while the pump is running.
For a closed loop system, the cooling water supply should be arranged as shown in the figure below.
M
M
F000156B
1
2
3
4
5
6
7
1.
Cooling water supply
2.
Expansion tank
3.
Flow meter
4.
Circulation pump
5.
Coolant in
6.
Coolant out
7.
Heat exchanger
Item
Notes
Cooling water supply Incoming supply should be equipped with a vacuum valve. It should also be
separated from the cooling circuit with a non-return (check) valve.
Expansion tank
Equipped with a level regulator. The tank is used to fill up the system at start-up,
and then acts as an expansion tank.
Product Description
36
C3300/6x5, C/R3231, C3240, C3306, C3312, C3351, C3356, C3400, C3501, C3531, C3602, C3800 Installation,
Operation and Maintenance Manual