Remote Control - Description of Commands
Commands and Queries
4
4-21
Example(s)
CALC:INT:STAR:TIME 2002,01,12,12,30,00
CALC:INT:STAR:TIME? Response:
2002,01,12,12,30,00
Invalidates
-
Invalidated by
-
CALCulate:INTegral:STOP:SOURce CMD | TIME | MAN | TINTerval
Description
Specifies integration stop condition.
Stopping integration does not reset the integrated values to zero.
Parameter(s)
CMD
Integration will stop upon receipt of the CALCulate:INTegral:STOP[:IMMediate]
command.
TIME
Integration will stop at a time specified by command CALCulate:INTegral:STOP:TIME
MAN
Integration will stop when user presses F2 key on the front panel from within integration
measurement screen of the instrument
TINTerval
Integration will stop after the interval specified with CALCulate:INTegral:STOP:TINTerval
elapses from the start of the integration.
*RST state
CMD
Example(s)
CALC:INT:STOP:SOUR CMD
CALC:INT:STOP:SOUR? Response:
CMD
Invalidates
-
Invalidated by
-
CALCulate:INTegral:STOP[:IMMediate]
Description
This command immediately stops integration.
Stopping integration does not reset the integrated values to zero.
Attempt to start integration with this command when
CALCulate:INTegral:STARt:SOURce is not set to CMD will generate error –221,
“Settings conflict”
Parameter(s)
-
Содержание NORMA 4000 Operators
Страница 6: ...Remote Control Users Guide iv ...
Страница 8: ...Remote Control Users Guide vi ...
Страница 10: ...Remote Control Users Guide viii ...
Страница 12: ...Remote Control Users Guide 1 2 Output Unit 1 13 Command Sequence and Command Synchronization 1 14 ...
Страница 26: ...Remote Control Users Guide 2 2 ...
Страница 38: ...Remote Control Users Guide 3 2 ...
Страница 50: ...Remote Control Users Guide 4 2 ...
Страница 150: ...Remote Control Users Guide 4 102 ...
Страница 152: ...Remote Control Users Guide 5 2 ...
Страница 160: ...Remote Control Users Guide 6 2 ...
Страница 184: ...Remote Control Users Guide 6 26 ...