Advanced Configuration
Input/Output 0
is a control signal for the camera heater circuits. The
Heater_GPIO44
output signal
performs internal functions and should not be changed.
The illustration at the right shows the default settings
for the input signal channel,
Input/Output 1
.
•
The Label setting can be changed to reflect more
specific alarm information which can then appear in
VMS systems such as FLIR Latitude.
•
The
GPIO Name
determines the circuit point for
the GPIO driver and must not be changed.
•
Set
GPIO Logic
to Positive for a normally open
switch signal (circuit closes for alarm), Set
GPIO
Logic
to Negative for a normally closed switch
signal (circuit opens for alarm).
The illustration at the right shows the default
settings for the output signal channel,
Input/Output
2
.
•
The
Label
setting can be changed to reflect
more specific alarm information which can then
appear in VMS systems such as FLIR Latitude.
•
The
GPIO Name
determines the circuit point for
the GPIO driver and must not be changed. Set
an
Initial Value
(On or Off) for this output signal.
•
The
Output Reset Interval
is used to
automatically reset the output signal after a set
time. Setting the value to 0 prevents the output
from resetting automatically after a timeout. See also the Alarm Manager GPIO Output State
Mode parameter,
GPIO Output from Motion Alarm, pg. 56
.
•
Set Alarm Output
GPIO Logic
to Positive for a normally open switch signal (circuit closes for
alarm), Set
GPIO Logic
to Negative for a normally closed switch signal (circuit opens for alarm).
Scroll to the bottom of the page and click on the
Save
button to save changed settings. Changes will not take
effect until the server is stopped and started.
Refer to the
how to combine the GPIO inputs and outputs with
Output duration
Click Save
Stop and Start Server