6 Installation of FLUXUS G800
36
UMFLUXUS_G8V4-6-1EN, 2018-10-10
frequency output
(open collector)
G800P
F1: 2 (+)
F1: 1 (-)
U
ext
= 5...30 V
R
c
[k
Ω
] = U
ext
/I
c
[mA]
I
c
= 2...100 mA
I
off
= 0.8 mA
frequency output
(open collector)
G800P
F1: 2 (+)
F1: 1 (-)
U
ext
= 8.2 V
R
c
= 1 k
Ω
DIN EN 60947-5-6
(NAMUR)
binary output
(open collector)
(only with
frequency output)
G800P
B1: 6 (+)
B1: 5 (-)
U
ext
= 5...30 V
R
c
[k
Ω
] = U
ext
/I
c
[mA]
I
c
= 2...100 mA
I
off
= 0.8 mA
binary output
(open collector)
G800
G800L
G800P
G800LP
B1...B4:
6/8/10/12 (+)
B1...B4:
5/7/9/11 (-)
U
ext
= 5...24 V
R
c
[k
Ω
] = U
ext
/I
c
[mA]
I
c
= 1...4 mA
binary output
(Reed relay)
G800
G800L
G800P
G800LP
B3/B4: 9/11
B3/B4: 10/12
U
max
= 48 V
I
max
= 100 mA
RS485
G800
G800L
G800P
G800LP
14 (A+)
13 (B-)
120
Ω
termination resistor
shield 15
Tab. 6.7: Circuits of the outputs
output transmitter
external
circuit
remark
internal circuit
connection
The number, type and connections of the outputs are customized.
R
ext
is the sum of all ohmic resistances in the circuit (e.g., resistance of the conductors, resistance of the amperemeter/voltmeter).
R
c
U
ext
Ref
+
-
R
c
U
ext
Ref
mA
+
-
R
c
U
ext
Ref
+
-
R
c
U
ext
Ref
+
-
a
b
+
-