manual – force
IQ
33
www.flexiforce.com
33
5.
Trouble shooting
5.1 Event message
Event message
Reason
OSE 1 ERROR
Safety device on OSE 1 port is defect KL3
OSE 2 ERROR
Safety device on OSE 2 port is defect KL4
SAFE.EDGE 1 ERR.
Safety device on SR1 port is defect KL2:1‐2
SAFE.EDGE 2 ERR.
Safety device on SR2 port is defect KL2:3‐4
4W‐PHOTOC. ERROR
Safety device on 4wire port is defect
DOOR SAFETY
Safety chain triggered, open circuit KL 7
MOTOR SAFETY
Safety chain triggered, open circuit KL 8
BLOCKED POSITIONER
Encoder communication error or no encoder KL18
INVERTER ERROR
Inverter communications error
BATTERY EMPTY
Dalmatic encoder reports its batteries are empty
OUT OF RANGE
Door moved past the end positions
UNAUTHORIS. MOVE
Door moved when it was not supposed to
DOOR TOO SLOW
Door did not move even though it should have
DOOR TOO FAST
Door was moving too fast (door speed monitoring)
WRONG DIRECTION
Door was moving in the wrong direction
ERROR BAD CONFIG
The stored configuration was missing/invalid
FACTORY RESET
Factory reset has been issued from the menu
ENDPOS. CHANGED
The end positions have been changed in menu
SEC.DEV. CHANGED
Safety device setting has been changed
REVERSED 3 TIMES
The door has reverse X times in a row and auto close has been disabled as a result
MEMORY FAULT RAM
Error has been detected during the RAM self test
MEM. FAULT FLASH
The flash CRC calculation has detected an error
MEM.FAULT EEPROM
The EEPROM CRC calculation has detected an error
SYSTEM POWER UP
System has been reset and is now starting up
PASSDOOR OPEN
Pass door has been opened while the door was moving
OSE 1 TRIGGERD
Safety device connected to KL 3 is activated
OSE 2 TRIGGERD
Safety device connected to KL4 is activated
SAFE. EDGE 1 TRIGGERD
Safety device connected to KL2 1‐2 is activated
SAFE. EDGE 2 TRIGGERD
Safety device connected to KL2 1‐2 is activated
4W‐PHOTOC. TRIGGERD
Safety device connected to KL5 is activated
5.2 trouble shooting
Problem
Solution
Error code won't disappear from display even if safety
edge are OK.
Clear history file in service settings
"Blocked positioner"
Adjust limit switch type/ check encoder connection
"Blocked out of range / stutter mode"
Use safety chain/crank or hand to move the door in right
position.
Operator is not moving, but you can hear the contact
switch clicking
‐ Check Fuses F1,F2 and F3
‐Check incoming Power (230V between N en L)
Not possible to adjust end positions
‐ Could happen after using the quick release.
Lock the door in position by moving it a little by hand.
‐ Check encoder settings
display without text
Check connection cable between cover and controlbox.
The red stripe on the flatcable has to be on the left side.
Quick release won't work
Make sure there is tension on the cables and the springs.
Bottom adjustment can be to tight on the floor.
Safety edge won't work
If you have mechanical limit switch, make sure you have
connected KL19 pin 5 and 6. You can connect them
together. Plug power back on.
Can't shut of Force IR
Make sure that If you use an optosensor
both transmitters are on the same side of the door.
ForceLC2 react spontaneously
Make sure the door covers up all the led's
Operator won't go up/down only buzzing noise
230V operator:Check if wire W from KL10 is connected to
the blue wire in the motor.
400V operator: check the 3 phases and the fuses.
Forgot the password
Contact your supplier.
Содержание ForceIQ Force100XC
Страница 1: ...forceIQ manual manual version 3 0 software version 1 147 c 1 DEF5000 EN ...
Страница 34: ......
Страница 35: ...manual forceIQ 35 www flexiforce com 34 Appendix 6 1 Additional function terminals ...
Страница 36: ...manual forceIQ 36 www flexiforce com 35 Terminal group A Terminal group B ...
Страница 37: ...manual forceIQ 37 www flexiforce com Terminal group C Terminal group D ...