background image

6

Fläkt Woods 

 

FIFLO  EN  2014.09

All rights reserved.

Control System FICO-128

INSTALLATION, USE AND MAINTENANCE

4 Control unit FCLA-128

1

Supply connection AC 230 V

2

Connection of fan interlocking FAN 1 (Group 1) and FAN 2 (Group 2)

3

Connection of output summation alarm for FIRE (8 = NO, 9 = C and 10 = NC)

4

Connection of output summation alarm for SERVICE (11 = NO, 12 = C and 13 = NC)

5

Input for external interlocking. Needs no acknowledging at control unit FCLA-128.

6

Input for external fire alarm. Alarm must be acknowledged at control unit FCLA-128.

7

Connectors for communication loop between control unit and communication units/relay units

8

Connectors for communication loop to parent system for control and monitoring

9

Connector (RJ45) for updating control unit FCLA-128

10

LINK 1

Indicates data transfer in comm. loop 1, flashes green

LINK 2

Indicates data transfer in comm. loop 2, flashes green

MODBUS

Indicates data transfer in MODBUS, flashes yellow

SYSTEM

Indicates voltage, illuminates green

11

AUTO/STANDBY

Illuminates green when in use

Flashes green in STANDBY

FIRE ALARM

Flashes red for alarm

Illum. red for acknowledged alarm

EXTERNAL ALARM

Flashes red for external fire alarm

Illum. red for acknowledged alarm 

INTERLOCK

Illum. red for active external interlocking

SERVICE ALARM

Flashes yellow for service alarm

FAN STOPPER

Illum. red for activated fan interlocking

COM ERROR

Flashes red for communication error

L

N

PE

4

5

6

7

230 VAC

FAN A FAN B

8

9

10

11

12

13

14

15

19

20

21

22

23

24

25

26

18

16

17

FIRE

SERVICE ILOCK EXT.

LINK 1

LINK 2

Max 24V/3A

INPUTS

Max 32 UNITS/LINK

ESC

EDIT

ENTER

INFO

ALARM

RESET

AUTO/STANBY

DAMPER TEST

FIRE ALARM

EXTERNAL ALARM

INTERLOCK

COM ERROR

FAN STOPPED

SERVICE ALARM

FCLA-128

FICO

MODBUS

SLAVE

Max 230VAC/3A

AUX

3

5

7

8

1

2

4

9

LINK1

LINK 2
MODBUS

SYSTEM

10

6

11

FIRE DAMPER CONTROL UNIT

LINK1

LINK 2
MODBUS

SYSTEM

Содержание FICO FCLA-128

Страница 1: ...Cotrol system FICO 128 Installation use and maintenance 09 2014...

Страница 2: ...s into use 11 9 15 10 Adding changing fan groups 16 11 Controlling operating status 16 12 Manual test of dampers communication units and groups 17 13 18 14 Adding a communication unit to the system 19...

Страница 3: ...nk 2 You can choose between three alternative smoke detectors Siemens R k ga SOS2 or Calectro UG 3 or Calectro EVC PY DA When Siemens R k ga SOC2 is used you can adjust the sensitivity of the detector...

Страница 4: ...ication to parent system Supply 230 V Output re alarm Output service alarm Interlocking FAN2 Interlocking Supply 230V Supply 230V Supply 230V FICO FCLA 128 FCBA 2 FCBA 2 FCBA 2 FCBA 2 Communication to...

Страница 5: ...CBA 2 FCBA 2 FCBA 2 FCBA 2 FCBA 2 FCFA 1 FCFA 1 Communication to parent system Supply 230 V Output re alarm Output service alarm Interlocking of fan FAN1 Group A Interlocking of fan FAN2 Group B Inter...

Страница 6: ...n LINK 2 Indicates data transfer in comm loop 2 ashes green MODBUS Indicates data transfer in MODBUS ashes yellow SYSTEM Indicates voltage illuminates green 11 AUTO STANDBY Illuminates green when in u...

Страница 7: ...ht switch 9 Updating of communication unit 10 Connectors for damper motors and smoke detectors 11 LEDs indicating operating status LED indicates open damper with illuminating green LED indicates close...

Страница 8: ...munication loop input and output 4 LEDs indicating operating status 5 Address switch 6 Updating of relay unit 7 Explanations of address switch 8 End resistor of communication bus activated in last com...

Страница 9: ...nect Calectro UG 3 to connectors G1 2 and M1 1 NOTE Do not forget the end resistor between connectors 1 and 5 in smoke detector NOTE Connect one smoke detector per input and max two per communication...

Страница 10: ...trol unit FCLA 128 after resetting central re alarm Connectors for external interlocking Needs no acknowledging at control unit FCLA 128 Remove jumper at connectors 14 and 15 if you are using input fo...

Страница 11: ...it is advisable to do it at this point before continuing See Chapter 6 Item 7 2 In order to facilitate start up and to have automatic reading of communication unit relay unit addresses they must alway...

Страница 12: ...day using the arrow keys then press ENTER to nish 11 Setting time Press ARROW DOWN once to go to Time press EDIT set hours and minutes using the arrow keys then press ENTER to nish Press ESC to contin...

Страница 13: ...to activate communication unit with address 03 Press ARROW DOWN press EDIT once press ARROW UP once then press ENTER Group A is always preselected to change fan group see Chap ter 10 If your system ha...

Страница 14: ...est Press EDIT set hours and minutes using the arrow keys press ENTER to nish Go to Test interval how often do you want the dampers to be tested Press EDIT and then ARROW UP select desired damper test...

Страница 15: ...ystem is set to Standby through System mode on the control unit The system must always be set to Standby before changing con guration 1 Log in if you already have not done so see Chapter 9 1 Go to the...

Страница 16: ...o to the Con g system menu select System and press ENTER 3 To change the Group of for example communication unit 03 Highlight the line of address 03 press EDIT once press AR ROW RIGHT press EDIT once...

Страница 17: ...cation unit press ESC and reselect the Test maintenance menu if you are testing other communica tion units The dampers connected to the communication unit are now tested and the fan relay connected to...

Страница 18: ...g the arrow keys then press ENTER Go to Service mode and press ENTER 2 Use the arrow keys to select the communication unit you want to shut off press EDIT and then ENTER The communication unit is now...

Страница 19: ...earlier the last one in the communication loop NOTE Each loop shall have only one activated end resistor 4 Set communication unit address using the address switches 5 Connect voltage to the communica...

Страница 20: ...ENTER 16 Select line with address for example 04 and activate it using the arrow keys Press EDIT twice Press ARROW UP and then ENTER 17 Fan Group A is always preselected Do you want to change fan Grou...

Страница 21: ...the communication loop NOTE Each loop shall have only one activated end resistor 4 Using the address switch set the desired Group for the relay unit Address 1 Group C in this example Address 2 Group...

Страница 22: ...ARROW UP until you are at the new fan Group C that you have chosen item 4 above Press ENTER and then ESC twice 17 Enter the Group menu to activate Group C 18 Select the line for R1 relay unit 1 press...

Страница 23: ...E Separate activation for left L and right R side of com munication unit 7 Connect smoke detector Siemens SOS2 to connectors G1 2 M1 1 and B1 NOTE Connect one smoke detector per input and max two per...

Страница 24: ...it at the communication unit FCBA 2 NOTE Separate activation for left L and right R side of com munication unit 7 Disconnect smoke detector Siemens SOS2 at connectors G1 2 M1 1 and B1 8 Disconnect Cal...

Страница 25: ...system and press ENTER 4 Go to System and then press ENTER 5 Use ARROW DOWN to go to the line to be deleted and press EDIT twice Press ARROW DOWN and then ENTER 6 Press ARROW RIGHT to remove Group lin...

Страница 26: ...munication fault situation not acknowledged at FCLA 128 SERVICE ALARM illuminates yellow in a communication fault situ ation acknowledged at FCLA 128 SERVICE ALARM ashes yellow when the system is in S...

Страница 27: ...LED indicates that damper is stuck between end positions 3 LED ashes red when a smoke detector has tripped re 4 LED ashes yellow in case of service alarm from smoke detec tor 5 LED illuminates green w...

Страница 28: ...Log in on the control unit using the arrow keys and then press ENTER 2 Log into the system using code 2000 Use the arrow keys to select a number and press ENTER after each number If your code was corr...

Страница 29: ...ss ENTER 4 Go to the System mode menu using the arrow keys and press ENTER 5 Select Mode and press EDIT and then press ARROW DOWN 6 Press ENTER 7 The whole system is now in Standby press ESC dampers c...

Страница 30: ...system documentation Installation Communication unit FCBA 2 Left Right No Damper Smoke detector Damper Smoke detecto Drawing identi ers Drawing identi er of control unit FCLA 128 Damper test interval...

Страница 31: ...31 INSTALLATION USE AND MAINTENANCE Fl kt Woods FIFLO EN 2014 09 All rights reserved Control System FICO 128 Communication unit FCBA 2 No Left Right Damper Smoke detector Damper Smoke detector...

Страница 32: ...FICO 128 installation instructions 9498EN 09 2014 All rights reserved Fl kt Woods Oy Kalevantie 39 FI 20520 Turku FINLAND Tel 358 20 442 3000 www aktwoods com...

Отзывы: