Control System FICO-128
INSTALLATION, USE AND MAINTENANCE
4 Control unit FCLA-128
1
Supply connection AC 230 V
2
Connection of fan interlocking FAN 1 (Group 1) and FAN 2 (Group 2)
3
Connection of output summation alarm for FIRE (8 = NO, 9 = C and 10 = NC)
4
Connection of output summation alarm for SERVICE (11 = NO, 12 = C and 13 = NC)
5
Input for external interlocking. Needs no acknowledging at control unit FCLA-128.
6
Input for external fire alarm. Alarm must be acknowledged at control unit FCLA-128.
7
Connectors for communication loop between control unit and communication units/relay units
8
Connectors for communication loop to parent system for control and monitoring
9
Connector (RJ45) for updating control unit FCLA-128
10
LINK 1
Indicates data transfer in comm. loop 1, flashes green
LINK 2
Indicates data transfer in comm. loop 2, flashes green
MODBUS
Indicates data transfer in MODBUS, flashes yellow
SYSTEM
Indicates voltage, illuminates green
11
AUTO/STANDBY
Illuminates green when in use
Flashes green in STANDBY
FIRE ALARM
Flashes red for alarm
Illum. red for acknowledged alarm
EXTERNAL ALARM
Flashes red for external fire alarm
Illum. red for acknowledged alarm
INTERLOCK
Illum. red for active external interlocking
SERVICE ALARM
Flashes yellow for service alarm
FAN STOPPER
Illum. red for activated fan interlocking
COM ERROR
Flashes red for communication error
L
N
PE
4
5
6
7
230 VAC
FAN A FAN B
8
9
10
11
12
13
14
15
19
20
21
22
23
24
25
26
18
16
17
FIRE
SERVICE ILOCK EXT.
LINK 1
LINK 2
Max 24V/3A
INPUTS
Max 32 UNITS/LINK
ESC
EDIT
ENTER
INFO
ALARM
RESET
AUTO/STANBY
DAMPER TEST
FIRE ALARM
EXTERNAL ALARM
INTERLOCK
COM ERROR
FAN STOPPED
SERVICE ALARM
FCLA-128
FICO
MODBUS
SLAVE
Max 230VAC/3A
AUX
3
5
7
8
1
2
4
9
LINK1
LINK 2
MODBUS
SYSTEM
10
6
11
FIRE DAMPER CONTROL UNIT
LINK1
LINK 2
MODBUS
SYSTEM