11
INSTALLATION, USE AND MAINTENANCE
Fläkt Woods
FIFLO EN 2014.09
All rights reserved.
Control System FICO-128
8 Taking FCLA-128 with its FCBA-2 communication
units into use
Example of taking into use a system with three communication units, all of which are to be connected to fan interlock-
ȱ ȱǯȱȱȱȱȱȱȱǰȱ ȱȱȱęǰȱȱȱ¢ȱȱȱȱȱ
Chapter 9; with more than two groups, Chapter 13 as well.
1
Before starting control unit settings, all installations of periph-
eral components shall be completed. See Chapters 6 and 7.
If addresses were not set in communication units when install-
ing them, it is advisable to do it at this point before continuing.
See Chapter 6, Item 7.
2
In order to facilitate start-up and to have automatic reading of
communication unit / relay unit addresses, they must always
be switched on before the control unit.
3
Switch on the control unit FCLA-128.
If you forgot to switch on the communication units / relay units be-
fore the control unit, press
UPDATE
at communication unit / relay
unit.
4
Press
ENTER.
5
Go to
Log in
using the arrow keys, and press
ENTER
.
FICO
FCLA-128
FCBA-2
Adr.01
FCBA-2
Adr.02
FCBA-2
Adr.03
TF
FF
Output fire alarm
Output service alarm
Interlocking of fan (Group A)
Supply 230V
Group A
Supply 230V
Supply 230V
Supply 230V
UPDATE
During any configuration, the system shall be in Standby. See Chapter 9.2