13
INSTALLATION, USE AND MAINTENANCE
Fläkt Woods
FIFLO EN 2014.09
All rights reserved.
Control System FICO-128
15
Under the
System
menu you must activate the communication
units (
En
).
Press
EDIT
twice.
16
Press
ARROW UP
to activate communication unit with ad-
dress 01, then press
ENTER
.
Group A is always preselected (to change fan group,
see chapter 10).
17
Press
ARROW DOWN
to activate the next communication unit
with address 02.
18
Press
EDIT
once, press
ARROW UP
once, then press
EN-
TER
.
Group A is always preselected (to change fan group, see Chap-
ter 10).
19
Continue to activate communication unit with address 03.
Press
ARROW DOWN
, press
EDIT
once, press
ARROW UP
once, then press
ENTER
.
Group A is always preselected (to change fan group, see Chap-
ter 10). If your system has several communication units, re-
peat the procedures until you have activated them all.
20
The display looks like this when you have finished.
If you want more fan groups, see Chapter 10.
21
Press
ESC
three times.
Go to
Save config and Exit
and press
ENTER.
22
To start the system you must go to
System mode
menu and
then press
ENTER
.
Press
ARROW UP
to come to
System mode
, then press
EN-
TER
.
23
Press
EDIT
, then
ARROW UP
, and finish with
ENTER
. The
system will start, dampers open and the interlocking contact to
fan will disconnect when the dampers are open.
24
Press
ESC.