background image

 

 

CONTENTS 

Certified for shock and electrical fire hazard only. 

 

SAFETY CONSIDERATIONS 

Read  and  follow  instructions  carefully.  Follow  all  local 
electrical  codes  during  installation.  All  wiring  must 
conform  to  local  and  national  electrical  codes.  Improper 
wiring or installation may damage Air Cleaner. 

Understand  the  signal  words  WARNING  and 

CAUTION which are present in the Owner’s Manual. 

WARNING  and  CAUTION  signifies  a  hazard  which 

could result in property damage, personal injury or death.

 

Installation  and  servicing  of  Electronic  Air 

Cleaners  can  be  hazardous.  Only  trained  and 
qualified  service  personnel  should  install,  repair,  or 
service Electronic Air Cleaners. 

Homeowners or untrained personnel can perform 

the  basic  maintenance  functions  of  cleaning  and 
replacing filters. 

When  working  on  air  cleaning  equipment, 

observe precautions in the manual, labels attached to 
the unit, and other safety precautions that may apply. 
Follow  all  safety  codes.  Wear  safety  glasses  and 
work gloves. 

 

WHAT THE ELECTRONIC AIR CLEANER DOES 

Your High Efficiency Electronic Air Cleaner has been 

designed  to  remove  atmospheric  and  household  dust, 
coal  dust,  insecticide  dust,  mites,  pollen,  mold  spores, 
fungi,  bacteria,  viruses,  pet  dander,  cooking  smoke  and 
grease,  tobacco  smoke  particles,  and  more  down  to  .01 
micron (.01 micron = 1/2,540,000 of an inch). 

BENEFITS 

Helps provide relief for allergy or asthma suffering. 
Helps  prevent  damaging  black  dust  from  staining 
walls  and  furnishings,  reducing  the  amount  of  time 
and money spent cleaning and redecorating. 
Helps  eliminate  unpleasant  odors  (with  use  of  
Carbon Filters). 
Helps  protect  heating/cooling  equipment,  prolonging 
the operating efficiency. 

HOW IT WORKS

 

The  High  Efficiency  Electronic  Air  Cleaner  operates 

on  the  principle  of  electrostatic  precipitation.  Millions  of 
airborne pollutants are carried through the return air ducts 
of  the  heating/cooling  system  and  treated  through  four 
stages of filtration. 

The 

prefilters  (2)

  remove  all  large  visible  particles 

such  as  lint.  Smaller  particles  then  pass  through  a 

two-

stage  electrostatic  collecting  cell  (2).

  First,  particles  are 

given a powerful positive electrical charge by the ionizing 
wires. Second, charged particles move into the collecting 

IMPORTANT:

    Please  read  entire  instructions  before 

installing the Electronic Air Cleaner. 

WARNING  

Before  beginning  any  installation  or  modification,  be 
certain  that  the  main  line  electrical  disconnect  switch  is 
in 

OFF

  position.  Electric  shock  could  result.  Tag 

disconnect switch with suitable warning labels.  

 

SAFETY CONSIDERATIONS 

WHAT THE ELECTRONIC AIR CLEANER DOES 

BENEFITS 

HOW IT WORKS 

SPECIFICATIONS 

COMPONENTS 

INSTALLATION 

3-5 

Static Pressure 

Location 

Installation Location With Humidifier 

Installation Location With Air Conditioner 

Electronic Air Cleaner Installation 

Wiring 

SYSTEM CHECK 

OPERATION 

WHITE DUST 

MAINTENANCE 

Cell and Prefilter Cleaning 

Activated Carbon Filter Replacement 

SERVICE 

7-10 

Quick Check 

Testing For High Voltage At Power Board 

Measuring High Voltage At Power Board 

Replacing Performance Light 

Replacing A Power Board 

Testing Air Proving Switch (APS) 

Replacing An Air Proving Switch (APS) 

Testing The 24 V Transformer 

Replacing The 24 V Transformer 

Setting Voltage Of Power Board 

Setting Voltage Without High Voltage Meter 

Testing For Voltage At The Cell 

Testing Cell For Bad Contacts 

Testing Cell With An Ohmmeter 

Removing Power Box 

10 

Replacing A Tungsten Ionizing Wire 

10 

EXPLODED VIEW 

10 

PARTS LIST 

11 

TROUBLESHOOTING GUIDE 

12 

WARRANTY 

15 

 

Fig. 1 

2 Prefilter 

1 Dirty Air 

3 Ionizing Section 

4 Collecting Cell Plates 

6 Clean Air to Heating/ 
Cooling System 

5 Carbon Filters (3) 
(optional) 

Содержание SASD10-2

Страница 1: ...i bacteria viruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unpleasant odors Electronic Air Proving Switch for quick wiring optional Dual Indicator Lights show Air Cleaner is working at a glance Galvanized Steel Cabinet for solid vertical or horizontal...

Страница 2: ...e of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 remove all large visible particles such as lint Smaller particles then pass through a two stage electrostatic collecting cell 2 First particles are given a powerful positive electrical charge by the io...

Страница 3: ...ir Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fan compartment as possible This location provides the most even airflow across the collecting cells and allows the Air Cleaner to keep the system motor and blower clean The installation can be vertical or horiz...

Страница 4: ...ype humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Whenever possible the Air Cleaner should be installed upstream of the cooling coil This location will clean the air before it reaches the evaporator coil 4 MODEL DIMENSIONS in cm A B C D E F G H SASD10...

Страница 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applicable codes and standards The voltage of the power source must match the voltage indicated on the Air Cleaner The Air Cleaner must operate ONLY when the system fan is running Make sure the Air Cleaner i...

Страница 6: ...with DAX Detergent or a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX Detergent and dunk cells up and down until water is dirty 3 Rinse cells well with hot water maximum 120 F 49 C 4 To remove contaminate from the ionizing wires use an old tooth...

Страница 7: ...e from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells installed the door closed and the system fan running The Air Cleaner should be on at least 5 minutes to allow voltage to stabilize The cells and ionizing wires must be clean 2 Remove the cover from powe...

Страница 8: ...board is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor is properly set down to the bottom of the plastic bushing in the front of the power box To check the APS for proper operation remove the collecting cells turn the unit ON without the fan on The power ...

Страница 9: ... voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not available this method can be used This will only set an approximate voltage After using this method the voltage should be reset with a high voltage meter as soon as possible 1 Remove power box cover ...

Страница 10: ...ove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Replacement wires are cut to the correct length and have eyelets at each end for easy replacement 1 Turn OFF power to Air Cleaner 2 Remove cell from Air Cleaner 3 Remove all parts of broken wire from the...

Страница 11: ...9 D1 0509 D0 0509 D1 0509 11 Power Box Complete No Cover Depends on options with power box 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0603 15 Collecting Cell D0 0400 D1 0400 D2 0400 D8 0400 16 Cell Handle R1 0484 R1 0484 R1 0484 R1 0484 17 Door with Plastic Clip Handle D0 0632 D1 0632 D2 0632 ...

Страница 12: ...h needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plates...

Страница 13: ...r basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to keep track of your cleaning schedule DATE CLEANED DATE CLEANED DATE CLEANED 13 ...

Страница 14: ...NOTES 14 ...

Страница 15: ...anties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor dealer or other person whatsoever FIVE SEASONS COMFORT LIMITED WILL NOT BE RESPONSIBLE FOR 1 Normal maintenance as outlined in the Owner s Manual including cleaning of electronic collecting cells and or replacement of carbon filters 2 Damage or repairs required as a consequence of faulty instal...

Страница 16: ...d of the furnace or air handler ensure that there is 220 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage to the terminals in the low speed mode so the Air Cleaner will not function The green Performance Indicator Light will not turn on The Air Cleaner performs best when the system fan is on FAN ON or Co...

Отзывы: