background image

 

 

3.  Push the light out through front of power box. 
4.  Push the new light into the power box. 
5.  Connect the wiring to the LED terminals on the power 

board.  P3  -  red;  P4  -  black.  Route  the  wires  away 
from the high voltage wires or contacts. 

6.  Replace cover. 
7.  Return power to Air Cleaner. Test light. 

 
Replacing A Power Board 

Before replacing the power board, turn 

OFF

 power to 

the Air Cleaner at the source or remove the plug. 
1.  Remove the power box cover. 
2.  Disconnect wiring from the  LED, HV1, HV2 and 24 V 

terminals. Make note of position of wires. 

3.  Remove the three hex nuts from the power board. 
4.  Remove the power board from the studs. 
5.  Place the new board onto studs with the 24 volt input 

close to the transformer. 

6.  Replace the hex nuts removed in Step 3. Ensure the 

star  washer  is  in  place  over  the  steel  spacer  at  the 
ground  location  on  the  power  board.  For  proper 
grounding the  washer must be located on the top of 
the steel spacer, under the power board. 

7.  Reconnect  wiring  to  LED,  HV1,  HV2,  and  24  V 

terminals on the new power board. See Fig. 5. 

8.  Return power to Air Cleaner. Test power board. 
9.  Replace power box cover. 

Note:

  The power board has been set before shipping. It 

is  not  usually  necessary  to  reset  the  voltage  to  the  new 
load. If you do need to adjust the voltage refer to Setting 
Voltage of Power Board section for more information.

 

 

Testing Air Proving Switch (APS) 

The  APS  sensor  must  sit  in  the  plastic  bushing  to 

operate  correctly.

 

The  sensor  is  very  sensitive  and 

operation may be affected by cold ambient temperatures, 
an  air  exchanger,  or  a  fresh  air  duct  connected  to  the 
return air duct just upstream of the Air Cleaner. 

The  APS  uses  a  Triac  in  its  output  circuit,  which 

affects  the  voltage  sine  wave.  Using  a  regular  digital 
voltmeter may give a false reading. To check the output 
from the APS, use a true RMS (root mean square) meter 
to  measure  the  output  at  terminals  1  and  4  of  the  APS. 
The  output  should  be  between  210  and  240  VAC, 
depending on the airflow across the sensor. 

A 220 volt neon lamp may be used to test the output 

of the APS. Place the leads of the lamp across terminals 
1  and  4  of  the  APS.  If  the  lamp  lights,  the  voltage  is 
sufficient for operation. 

Do not use performance light.

 

When the Air Cleaner is turned on without airflow, the 

APS sensor heats up, and after 20-30 seconds opens the 
circuit to turn off the power board. When the fan starts up 
(the  sensor  is  cooled),  the  circuit  will  close,  the  power 
board  is  turned  on,  and  the  performance  light  will  come 
on. 

The  light  on  the  power  switch  will  be  lit  even  when 

the APS is open. 

If  the  power  board  fails  to  come  on  with  the  fan  on, 

check that the sensor is properly set down, to the bottom 
of  the  plastic  bushing,  in  the  front  of  the  power  box.  To 
check the APS for proper operation remove the collecting 
cells,  turn  the  unit 

ON

  without  the  fan  on.  The  power 

board  should  come  on  immediately,  and  then  turn  off  in 
20-30 seconds as the sensor heats up. To check sensor, 
blow  directly  on  it lightly. This should activate the  power 
board  within  10  seconds.  Service  the  sensor  carefully. 
The sensor leads are 220 V. If the APS does not turn the 
power  board  and  performance  indicator  on,  by-pass  the 
APS  by  placing  a  jumper  between  wires  3  &  4  on  the 
APS. This removes the APS from the circuit. 
See Troubleshooting Guide for more information. 

Note:

 If the air flow through the Air Cleaner is less than 

360 CFM the APS sensor may not have enough air flow 
to  activate  the  Air  Cleaner.  See  Wiring  for  information 
how  to  wire  the  Air  Cleaner  to  the  EAC  module  of  the 
system. In very  low  air applications the  Air Cleaner  may 
need to be wired through the EAC contacts and the APS 
disabled by connecting wires 3 & 4 together. 
If  there  is  no  EAC  module  or  it  is  not  powered  on  low 
speed then a relay will have to be installed to activate the 
Air Cleaner when the fan starts. The APS will have to be 
disabled. 
 

Replacing An Air Proving Switch (APS) 

Before replacing the APS, turn 

OFF

 the power to the 

Air Cleaner at the source.  
1.  Disconnect wiring from terminals 1, 2, 3, and 4 on the 

APS. See Fig. 5. 

2.  Remove the circuit board from the studs by removing 

the two nuts. Do not remove the spacers. 

3.  Install the new APS on the studs and secure with the 

nuts.  Ensure  sensor  protrudes  only  to  the  bottom  of  
the plastic bushing. 

4.  Connect  wiring  to  terminals  on  APS.  See  Fig.  5. 

Wiring  from  the  power  switch  is  connected  to 
terminals  2  and  3.  Wiring  to  the  transformer  is 
connected to terminals 1 and 4. 

5.  Test the new APS. 

 
Testing The 24 V Transformer  

1.  Remove power box cover. 
2.  Disconnect  the  leads  of  the  24  V  transformer  from 

the power board. See Fig. 5. Do not short leads. 

3.  The  Air  Cleaner  should  be 

ON

.  The  system  fan 

should  be  running  on  high  speed.  The  access  door 
should be closed. 

4.  Measure  voltage  across  the  leads  with  a  voltmeter. 

Voltage should read 25 - 28 VAC. 

5.  If no voltage is present, check operation of the APS. 
6.  Reconnect leads to the power board. 
7.  Replace power box cover. 

 
Replacing The 24 V Transformer 

Before  replacing  the  transformer,  check  the 

resistance across the power board  24 V  input terminals, 

Содержание SASD10-2

Страница 1: ...i bacteria viruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unpleasant odors Electronic Air Proving Switch for quick wiring optional Dual Indicator Lights show Air Cleaner is working at a glance Galvanized Steel Cabinet for solid vertical or horizontal...

Страница 2: ...e of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 remove all large visible particles such as lint Smaller particles then pass through a two stage electrostatic collecting cell 2 First particles are given a powerful positive electrical charge by the io...

Страница 3: ...ir Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fan compartment as possible This location provides the most even airflow across the collecting cells and allows the Air Cleaner to keep the system motor and blower clean The installation can be vertical or horiz...

Страница 4: ...ype humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Whenever possible the Air Cleaner should be installed upstream of the cooling coil This location will clean the air before it reaches the evaporator coil 4 MODEL DIMENSIONS in cm A B C D E F G H SASD10...

Страница 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applicable codes and standards The voltage of the power source must match the voltage indicated on the Air Cleaner The Air Cleaner must operate ONLY when the system fan is running Make sure the Air Cleaner i...

Страница 6: ...with DAX Detergent or a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX Detergent and dunk cells up and down until water is dirty 3 Rinse cells well with hot water maximum 120 F 49 C 4 To remove contaminate from the ionizing wires use an old tooth...

Страница 7: ...e from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells installed the door closed and the system fan running The Air Cleaner should be on at least 5 minutes to allow voltage to stabilize The cells and ionizing wires must be clean 2 Remove the cover from powe...

Страница 8: ...board is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor is properly set down to the bottom of the plastic bushing in the front of the power box To check the APS for proper operation remove the collecting cells turn the unit ON without the fan on The power ...

Страница 9: ... voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not available this method can be used This will only set an approximate voltage After using this method the voltage should be reset with a high voltage meter as soon as possible 1 Remove power box cover ...

Страница 10: ...ove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Replacement wires are cut to the correct length and have eyelets at each end for easy replacement 1 Turn OFF power to Air Cleaner 2 Remove cell from Air Cleaner 3 Remove all parts of broken wire from the...

Страница 11: ...9 D1 0509 D0 0509 D1 0509 11 Power Box Complete No Cover Depends on options with power box 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0603 15 Collecting Cell D0 0400 D1 0400 D2 0400 D8 0400 16 Cell Handle R1 0484 R1 0484 R1 0484 R1 0484 17 Door with Plastic Clip Handle D0 0632 D1 0632 D2 0632 ...

Страница 12: ...h needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plates...

Страница 13: ...r basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to keep track of your cleaning schedule DATE CLEANED DATE CLEANED DATE CLEANED 13 ...

Страница 14: ...NOTES 14 ...

Страница 15: ...anties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor dealer or other person whatsoever FIVE SEASONS COMFORT LIMITED WILL NOT BE RESPONSIBLE FOR 1 Normal maintenance as outlined in the Owner s Manual including cleaning of electronic collecting cells and or replacement of carbon filters 2 Damage or repairs required as a consequence of faulty instal...

Страница 16: ...d of the furnace or air handler ensure that there is 220 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage to the terminals in the low speed mode so the Air Cleaner will not function The green Performance Indicator Light will not turn on The Air Cleaner performs best when the system fan is on FAN ON or Co...

Отзывы: