background image

 

 

Fig. 5 — Air Cleaner Schematic (with Air Proving Switch) 

Electronic Air Cleaner Installation 

1.  Remove  existing  equipment  filter.  Thoroughly  clean 

fan compartment and ductwork where Air Cleaner is 
to be installed. 

2.  Open  access  door.  Slide  filters  and  collecting  cells 

out of cabinet. 

3.  Place  cabinet  in  ductwork.  Holes  are  provided  to 

attach  cabinet  to  ductwork  or  equipment.  If  the 
adjoining  ductwork  is  flanged,  install  the  screws  so 
that the screw heads are inside the cabinet. This will 
help  prevent  damage  to  prefilter  and  carbon  filters 
during  removal  for  cleaning. 

Never

  put  screws  or 

rivets 

into 

the 

removable 

power 

box. 

When  the  air  duct  does  not  fit  the  Air  Cleaner 
opening,  a  gradual  transition  is  recommended  to 
reduce air turbulence though the air Air Cleaner and 
to  increase  its  efficiency.  There  should  not  be  more 
than  20º  of  expansion  used  on  each  side  of  the 
transition fitting. Do not reduce ductwork to a smaller 
Air Cleaner or it will increase the velocity of airflow. 

4.  If the Air Cleaner is installed adjacent to an elbow or 

angle  fitting,  turning  vanes  are  recommended  to 
improve air distribution across the collecting cells. 

5.  After the Air Cleaner has been installed, seal seams 

airtight  with  duct  tape  or  caulking  to  prevent  dust 
from entering the system. 

6.  Replace the prefilters in the track on the air entering 

side.  Place  the  carbon  filters  evenly  spaced  in  the 
track  on  the  air  exiting  side.  The  collecting  cells  are 
placed  between  the  tracks,  with  the  arrow  on  cell 
pointing  towards  the  fan.  The  cell  handle  may  need 
to  be  repositioned  if  the  airflow  is  in  a  different 
direction  than  the  left  to  right  set  up.  The  handle 
should face the door. Close access door. 

 
Wiring 

 

Wiring  should  only  be  performed  by  qualified  personnel 
only. All wiring must comply with all applicable codes and 
standards. The voltage  of the power source must match 
the voltage indicated on the Air Cleaner. The Air Cleaner 
must  operate 

ONLY

  when  the  system  fan  is  running. 

Make sure the Air Cleaner is properly grounded. 

If  the  air  cleaner  is  equipped  with  a  cord  and  plug, 

the air cleaner can be plugged into an outlet within 6 feet 
of  the  unit.  Do  not  use  an  extension  cord  if  the  outlet  is 
too  far  away.  Have  an  electrician  wire  in  a  new  outlet 
closer to the air cleaner.   

If  the  air  cleaner  is  not  equipped  with  a  cord,  then 

wire  the  Air  Cleaner  directly  to  a  220-240  V  power 
source,  preferably  to  the  same  source  that  is  supplying 
power to the furnace or air handler. The APS will power 
the Air Cleaner when there is sufficient airflow to activate 
the sensor. See Fig 5. 

Note:

  The  power  switch  will  be  lit  even  if  there  is  no 

airflow. 

If the unit  is to be  wired to the EAC contacts on the 

system  module,  check  that  there  is  sufficient  voltage  to 
the EAC contacts with the fan operating in all conditions. 
Some systems do not power the contacts on low speed. 
 

SYSTEM CHECK 

Perform the following system check before operation. 
1.  Replace  prefilters,  collecting  cells  and  carbon  filters. 

Close access door. 

2.  Turn  Air  Cleaner  power  switch 

ON

.  Ensure  system 

fan  is  operating.  Both  the  power  switch  light  and 
performance  indicator  light  should  be  lit.  The  power 
switch light indicates the Air Cleaner has unit voltage. 
The  performance  indicator  light  shows  that  the  Air 
Cleaner is operating. 

WARNING  

Electrical  shock  can  cause  injury  or  death.  Be  certain 
main line disconnect switch is off before wiring.  

Содержание SASD10-2

Страница 1: ...i bacteria viruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unpleasant odors Electronic Air Proving Switch for quick wiring optional Dual Indicator Lights show Air Cleaner is working at a glance Galvanized Steel Cabinet for solid vertical or horizontal...

Страница 2: ...e of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 remove all large visible particles such as lint Smaller particles then pass through a two stage electrostatic collecting cell 2 First particles are given a powerful positive electrical charge by the io...

Страница 3: ...ir Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fan compartment as possible This location provides the most even airflow across the collecting cells and allows the Air Cleaner to keep the system motor and blower clean The installation can be vertical or horiz...

Страница 4: ...ype humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Whenever possible the Air Cleaner should be installed upstream of the cooling coil This location will clean the air before it reaches the evaporator coil 4 MODEL DIMENSIONS in cm A B C D E F G H SASD10...

Страница 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applicable codes and standards The voltage of the power source must match the voltage indicated on the Air Cleaner The Air Cleaner must operate ONLY when the system fan is running Make sure the Air Cleaner i...

Страница 6: ...with DAX Detergent or a non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX Detergent and dunk cells up and down until water is dirty 3 Rinse cells well with hot water maximum 120 F 49 C 4 To remove contaminate from the ionizing wires use an old tooth...

Страница 7: ...e from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells installed the door closed and the system fan running The Air Cleaner should be on at least 5 minutes to allow voltage to stabilize The cells and ionizing wires must be clean 2 Remove the cover from powe...

Страница 8: ...board is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor is properly set down to the bottom of the plastic bushing in the front of the power box To check the APS for proper operation remove the collecting cells turn the unit ON without the fan on The power ...

Страница 9: ... voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not available this method can be used This will only set an approximate voltage After using this method the voltage should be reset with a high voltage meter as soon as possible 1 Remove power box cover ...

Страница 10: ...ove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Replacement wires are cut to the correct length and have eyelets at each end for easy replacement 1 Turn OFF power to Air Cleaner 2 Remove cell from Air Cleaner 3 Remove all parts of broken wire from the...

Страница 11: ...9 D1 0509 D0 0509 D1 0509 11 Power Box Complete No Cover Depends on options with power box 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0603 15 Collecting Cell D0 0400 D1 0400 D2 0400 D8 0400 16 Cell Handle R1 0484 R1 0484 R1 0484 R1 0484 17 Door with Plastic Clip Handle D0 0632 D1 0632 D2 0632 ...

Страница 12: ...h needle nose pliers gently pull contacts down or replace contacts Cells arcing excessively power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plates...

Страница 13: ...r basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to keep track of your cleaning schedule DATE CLEANED DATE CLEANED DATE CLEANED 13 ...

Страница 14: ...NOTES 14 ...

Страница 15: ...anties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor dealer or other person whatsoever FIVE SEASONS COMFORT LIMITED WILL NOT BE RESPONSIBLE FOR 1 Normal maintenance as outlined in the Owner s Manual including cleaning of electronic collecting cells and or replacement of carbon filters 2 Damage or repairs required as a consequence of faulty instal...

Страница 16: ...d of the furnace or air handler ensure that there is 220 Volt output from these terminals when the unit is run manually and is running on low speed Some manufacturers do not supply full output voltage to the terminals in the low speed mode so the Air Cleaner will not function The green Performance Indicator Light will not turn on The Air Cleaner performs best when the system fan is on FAN ON or Co...

Отзывы: