Generator Failure
Seite 54 Panda PMS 8.000 NE - 42 NE Manual.R04 - Kapitel B: Generator Failure
8.7.08
B.4.5 Check the Windings for Short Circuiting
Ensure that the generator has been switched off and cannot be inadvertently switched on. Dis-
connect the wires to the battery for this.
1. All wires in the junction box or - if necessary - in the circuit distribution box must be disconnec-
ted. Ensure that the wires are no longer carrying an electrical current, before being disconnec-
ted (see “Discharging the Capacitors” on Page 51.)
2. Remove the Bridges between "N"and "PE", so that the windings and casing do not come into
electrical contact.
3. Make a check, by means of a Multimeter, as to whether there is a current between the indivi-
dual winding terminals and the casing (PE).
The contacts to measured are not relevant to
the type of generator (see type plate):
HP1 - 50 Hz: L, Z
HP1 - 60 Hz: L, Z
HP3 - 50 Hz: L1, L2, L3
HP3 - 60 Hz: L1, L2, L3, 1, 2, 3, 4
DVS - 50 Hz: L1, L2, L3, L1’
DVS - 60 Hz: L1, L2, L3, L1’, 1, 2, 3, 4
The generator must be sent for a check to the factory or be re-winded locally, when a pass (beep)
should be detemined. Windings data can be requested for this, if it is necessary.
Fig. B.4.5-1: Generator type plate
B.4.6 Measuring the Inductive Resistance
An Ohm measurement of a winding does not always give reliable information concerning the
state of the winding. If there are resistance irregularities between the windings parts, this is a sure
sign that the winding is defective. This means the opposite cannot be concluded. This means a
winding can also be defective, if the resistance values between the windings parts do not show
great deviation.
Measurement of the inductive resistance gives a better reading. A Special measuring device is
necessary for this.
The inductivity is measured in the same manner as the resistance, i.e. the windings parts are
compared. The value of the inductive resistance is given in mH (milli Henry).
The correct values for the inductive resistance can be obtained from Table 4 on Page 110.
Note: The values are greatly dependent upon the measuring method (type of ohmmeter).
Содержание Panda PMS-HD 12-4KU
Страница 58: ...Generator Failure Seite 58 Panda PMS 8 000 NE 42 NE Manual R04 Kapitel B Generator Failure 8 7 08 Blank...
Страница 76: ...Maintenance Instructions Seite 76 Panda PMS 8 000 NE 42 NE Manual R04 Kapitel C Maintenance Instructions 8 7 08...
Страница 104: ...Installation Instructions Seite 104 Panda PMS 8 000 NE 42 NE Manual R04 Capture D Installation Instructions 8 7 08 Blank...
Страница 116: ...Tables Page 116 Panda PMS 8 000 NE 42 NE Manual Chapter E Tables HP3 120V 60 Hz DVS 400V 50 Hz DVS 120V 240V 60 Hz...
Страница 120: ...Tables Page 120 Panda PMS 8 000 NE 42 NE Manual Chapter E Tables...
Страница 122: ...Generator Data F 2 Capsule measurements...
Страница 148: ...Measurements Page 148 Panel Generator Control P6 RE0703_Kunde_eng R02 Chapter B Measurements 8 7 08 Intentionally Blank...