First 21128 Скачать руководство пользователя страница 5

ROTOTERM MR-TR

5

www.first.si

CONNECTION OF THE REGULATION MOTOR

After the regulation motor is mounted to the mixing valve (for mounting see chapter “Instructions for mounting the 

regulation motor”), connect the motor to the terminal pins in the connection box of the controller. Should the closing 

direction be changed, change the connecting wires on terminal pins 12 and 14.

We recommend the use of our regulation motors:

grey

black

grey

black

MV 120/09E

MV 120/210

MV 120/360

MV 120..540 (EUROMIX)

CONNECTING THE CIRCULATION PUMP

The controller controls the circulation pump whenever there is a signal for heating and shuts it off as soon as the 

heating water line is cooled down bellow the set temperature (see “Setting pump switch off” - parameter [c]). It shall 

be connected to terminal pins 10 and 11.

Recommendation:

As  an  extra  precaution  for 

under  floor  heating  we  recommend  use 

of regulation motor series MV 120/210 for 

mixing  valves  up  to  DN  40  or  series  MV 

120/360 for larger mixing valves. Advantage 

of these two regulation motors is, that it can 

be set an angle of opening of the mixing 

valve. This way the maximum temperature 

of  heating  water  coming  into  under  floor 

heating system can be limited.

Recommendation:

For under floor heating we recommend in stallation of an extra safety bimetal thermostat 

on the mixed flow line. The ther mo stat shall be set to some 50°C and shall switch off the 

cir cu lation pump after the tem pera ture in the heating wa ter line ex ceeds 50°C. The use of 

ther mo stat is rec ommended as precaution in order to prevent hot wa ter to breaking  into 

under floor heating system.

bi metal 

ther mo stat

SENSOR MOUNTING

All the connecting cables of temperature sensors and indoor units can be extended, but you have to some basic rules to 

consider:

 1. Sensors cables do not lead in parallel with the mains voltage cables (220V/50Hz). There can appears current stroke, which 

cause voltage induction and it can damage the controller or sensors. If there is no other way then parallel minimum distance is 10cm 

between them. It is allowed to guide the sensor’s cable perpendicular crossing voltage cables.

 2. If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance 

of 25V. It is installed by soldering at the point where the original sensor’s wire extended to the other cable wire (see Figure 2).

3. Extending the sensor cable is recommended by shielded telephone, shielded data or any other for that purpose cable cross section 

0.5 mm ² or more (for example JY (St) 1X 2X0,6). These cables prevent the transmission of interference or noise from the environment 

that would cause improper operation or to reset the controller. Most often is a shield of aluminium foil and extra noninsulated - shield 

wire. Connection should be undertaken in a manner described below (see Figure 1 and the recommendation of experts).

 4. By installation is necessary to provide mechanical protection of sensors and wires, and protection against atmospheric 

influences.

Recommendation of experts:

During the laying of cables is needed to 

decide the path-line, which is not near the 

high voltage or high frequency electrical 

sources (power cables, cables to various 

appliances: pump, motor actuators, boiler,...). 

Common  ground  at  one  point  is  first 

condition to operate without interference. It is 

recommended earthing of protective shield 

cable to the power connection, which is in 

the controller (the ground terminal) or in the 

control, distribution cabinet. The other end of 

the cable connected to the sensor should be 

equipped in accordance with the procedure 

in Figure 1 and these instructions.

On the side where is extended the original sensor, removable part of the insulation in the shielded wire turn back to connect cable 

shield. All together squeeze good, and by wrapping the insulating tape, taking care of protection shield wires do not extend the 

scope of the connection of two signal wires. Each protruding wire can become a source of new interference, that why it is necessary 

to make this connection especially with care. 

In this way it is assured the best possible protection of sensors, and save yourself a bunch of nerves and the spend time in case 

of any errors due to disturbances.

Figure: 2

VDR resistor

Thermo 

shrinkable tube

Sensor’s 

cable

Extending 

cable

Protection wire 

Signal wires

Signal wires

Protection wire turn 

back to cable shield and 

insulate them both

Insulated band

Figure: 1

Содержание 21128

Страница 1: ...display Code Description 21128 ROTOTERM MR TR plus Heating controller MR TR Room unit AS 2000 E sensors AF BSVF BF mounting kit 21131 ROTOTERM MR TR Heating controller MR TR sensors AF BSVF BF mounti...

Страница 2: ...t When used with radiator version the sensor is located into the boiler in order to prevent condensation or overheating of the boiler In case the boiler temperature falls bellow the condensing tempera...

Страница 3: ...5 The under floor sensor of the controller prevents the under floor to get too hot thus prevents the unpleasant feeling of warmth in your feet When used with radiator version the sensor is located in...

Страница 4: ...pins PIN CONNECTION 1 2 Put side air sensor AF 2000 3 4 Mixed flow sensor VF2000 grey colour 5 6 Room unit AS2000 5 9 6 9 7 8 Floor sensor BF2000 or boiler sensor KF2000 red colour 9 N Neutral condui...

Страница 5: ...ltage cables 2 If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V It is installed by soldering at the point where the...

Страница 6: ...se you don t have protection against floor overheating MOUNTING OF BOILER SENSOR KF 2000 for radiator heating only Mount the sensor into the cap next to the other boiler sensors In case of 4 way mixin...

Страница 7: ...ars Sensor cables shall not be placed parallel to live power supply cables as in case of electric shock there is danger of induced current which can damage the controller or room unit In case that pow...

Страница 8: ...fference Troom between actual room temperature and required room temperature When T2 BF KF key is pressed the display shows floor temperature or temperature in the boiler When T3 AF key is pressed the...

Страница 9: ...t can be modified by means of heating curve ascent or descent Range of parallel curve shift for heating curve 1 0 SELECTION OF HEATING CURVE Heating curves represent an interconnection between outside...

Страница 10: ...to This setting specifies the temperature at which the controller switches off the pump when mixing valve is already closed This function enables that all heating units are uniformly cooled down afte...

Страница 11: ...value of ratio Programming is executed in three procedures For easier understanding see the diagram on the following page First procedure set the ratio of heating curve and parallel shift Second proce...

Страница 12: ...Additionally it is equipped with room temperature display Room unit AS 2000 E has additional switch on the right side It makes possible to choose two heating regimes temperature control of mixed flow...

Страница 13: ...inutes 10 key for setting hours 11 key for setting the day of the week 12 key for input the program 13 key RESET deletes time and program 14 Slide switch for unit operation ON temperature control of m...

Страница 14: ...of operation There are two operating modes if the switch 14 in the ON position provides frost protection room temperature 8 10 C if the switch 14 in the OFF position heating is switched off closes mix...

Страница 15: ...o a lower temperature On the display appears symbol which indicates switching to higher temperature 2 First switching cycle for switching to higher temperature On display appears symbol for first sett...

Страница 16: ...xt switch cycle etc Temporary heating regime change Temporary change of regime is valid till next switch cycle When you re in automatic mode slide switch 2 in position AUTO press to change the regime...

Страница 17: ...to position AUTO program is not set See the example of program settings the program is incorrectly configured for each switch cycle to a higher temperature is followed switch cycle to a lower temperat...

Страница 18: ...T3 sensors If T2 or T3 key is pressed Er2 is displayed Sensor T2 or T3 short circuited Check T2 and T3 sensors The controller operating normally Sometimes it happens that the controller repeatedly re...

Отзывы: