ROTOTERM MR-TR

17

www.first.si

Before calling service

Most frequent faults which appear during operation of automatic regulation unit and are consequence of 

wrong settings or wrong connection.

Malfunctions, which are described in the table are all the result of incorrect installation and incorrect settings. You can remove them 

and you do not need to call service technician.

If eventually a change of operating mode of automatic unit appears which is not common, first check eventual faults of settings and 

installation. See Instructions for MR-TR controller and check if connection between controller and AS 2000 room unit is correctly 

performed.

Before starting up and if error occurs we recommend to first check the following:

-  is electric fuse in phase of automatic unit installed and if operates,

-  is main switch ON,

-  are all connections performed,

-  is fuel in reservoir or inlet gas valve open,

-  is heating really required - check outside temperature,

-  is boiler temperature high enough regarding setting of boiler condense point.

If all above specified conditions are fulfilled and you haven find the cause for fault, see the following table. In case you still can 

not find and eliminate the fault, call our authorised technician. 

AS2000-E

Problem

Solution

The display will appear EEE

Slide switch 2 is moved to the position  . Before setting the program is necessary 

to set the correct time and date.

Timer is not running  

Slide switch is in position   or  . Move it in position AUTO.

Time flashes

Time is not set.

The program is not running

- move slide switch 2 to position AUTO

- program is not set. See the example of program settings.

- the program is incorrectly configured:

- for each switch cycle to a higher temperature, is followed

switch cycle to a lower temperature

- for each switch cycle must be set the day or group days  

- make sure the time settings do not overlap

Display is beginning to fade

The batteries are exhausted. We recommend changing batteries before the start of 

each heating season (at least every 2 years).

ROTOTERM MR-TR

STATUS

POSSIBLE FAULT

REMEDY

At outside temp. +10°C the room is warm 

enough, at temp. -10° it is too cold.

Heating curve set too low.

Set the curve to higher value.

In room should be higher (day) temperature 

but is too cold.

- Timer settings.

- Digital timer - overlapping of 

  switch cycles 

- Check timer setting

Regulation motor does not rotate.

- No supply from controller

- Faulty motor

- Too hard (blocked) mixing 

  valve.

- Check terminal pins 17, 18 and 19,

- Check mixing valve and its rigidity.

Regulation motor rotates, mixing valve 

does not respond.

- Broken safety forks (only by 

MV120/09E,...)

- Broken lever on handle.

- Replace safety forks on handle,  

- replace handle.

- check handle end positions

Regulation motor does not stop in final 

positions.

- Valve handle displaced.

- Check final positions of the handle.

LED for valve opening 

( )

 is ON on 

controller, mixing valve is fully open, hot 

in the room

Interrupted

- outside sensor AF,

- mixed flow sensor VF,

- AS 2000 room unit .

Check

- resistance of AF,

- resistance of VF,

- room unit.

LED for valve closing ( )is ON on controller, 

mixing valve is closed, too cold in the room

Short circuited

- outside air sensor AF

- AS 2000 room unit 

- sensor VF

- under floor sensor BF

- slide switch in

 

 

position.

Check

- resistance of AF, VF and BF

- supply from AF, VF, BF and room unit

- set selector switch 5 to  

  position  .

Содержание 21128

Страница 1: ...display Code Description 21128 ROTOTERM MR TR plus Heating controller MR TR Room unit AS 2000 E sensors AF BSVF BF mounting kit 21131 ROTOTERM MR TR Heating controller MR TR sensors AF BSVF BF mounti...

Страница 2: ...t When used with radiator version the sensor is located into the boiler in order to prevent condensation or overheating of the boiler In case the boiler temperature falls bellow the condensing tempera...

Страница 3: ...5 The under floor sensor of the controller prevents the under floor to get too hot thus prevents the unpleasant feeling of warmth in your feet When used with radiator version the sensor is located in...

Страница 4: ...pins PIN CONNECTION 1 2 Put side air sensor AF 2000 3 4 Mixed flow sensor VF2000 grey colour 5 6 Room unit AS2000 5 9 6 9 7 8 Floor sensor BF2000 or boiler sensor KF2000 red colour 9 N Neutral condui...

Страница 5: ...ltage cables 2 If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V It is installed by soldering at the point where the...

Страница 6: ...se you don t have protection against floor overheating MOUNTING OF BOILER SENSOR KF 2000 for radiator heating only Mount the sensor into the cap next to the other boiler sensors In case of 4 way mixin...

Страница 7: ...ars Sensor cables shall not be placed parallel to live power supply cables as in case of electric shock there is danger of induced current which can damage the controller or room unit In case that pow...

Страница 8: ...fference Troom between actual room temperature and required room temperature When T2 BF KF key is pressed the display shows floor temperature or temperature in the boiler When T3 AF key is pressed the...

Страница 9: ...t can be modified by means of heating curve ascent or descent Range of parallel curve shift for heating curve 1 0 SELECTION OF HEATING CURVE Heating curves represent an interconnection between outside...

Страница 10: ...to This setting specifies the temperature at which the controller switches off the pump when mixing valve is already closed This function enables that all heating units are uniformly cooled down afte...

Страница 11: ...value of ratio Programming is executed in three procedures For easier understanding see the diagram on the following page First procedure set the ratio of heating curve and parallel shift Second proce...

Страница 12: ...Additionally it is equipped with room temperature display Room unit AS 2000 E has additional switch on the right side It makes possible to choose two heating regimes temperature control of mixed flow...

Страница 13: ...inutes 10 key for setting hours 11 key for setting the day of the week 12 key for input the program 13 key RESET deletes time and program 14 Slide switch for unit operation ON temperature control of m...

Страница 14: ...of operation There are two operating modes if the switch 14 in the ON position provides frost protection room temperature 8 10 C if the switch 14 in the OFF position heating is switched off closes mix...

Страница 15: ...o a lower temperature On the display appears symbol which indicates switching to higher temperature 2 First switching cycle for switching to higher temperature On display appears symbol for first sett...

Страница 16: ...xt switch cycle etc Temporary heating regime change Temporary change of regime is valid till next switch cycle When you re in automatic mode slide switch 2 in position AUTO press to change the regime...

Страница 17: ...to position AUTO program is not set See the example of program settings the program is incorrectly configured for each switch cycle to a higher temperature is followed switch cycle to a lower temperat...

Страница 18: ...T3 sensors If T2 or T3 key is pressed Er2 is displayed Sensor T2 or T3 short circuited Check T2 and T3 sensors The controller operating normally Sometimes it happens that the controller repeatedly re...

Отзывы: