ROTOTERM MR-TR

11

www.first.si

7. PARAMETER: [t]

Parameter [t] has two functions and depends on the type of selected controller (radiator of under floor type heating).

Radiator heating 

               from: 

to

7.1 TEMPERATURE OF BOILER CONDENSE POINT: [t]

When boiler has more users (mixing valves with pumps) or the boiler is under-di men sioned, condense frequently appear during 

morning start-ups in boiler and flues due to too high consumption, especially at radiator heating. For this reason the controller is 

equipped with KF boiler sensor, which reads boiler temperature. If the temperature of the boiler decreases under the set value, the 

controller begins closing the mixing valve and enables the burner to quickly heat the boiler to set temperature. The temperature of 

condense point can be set between 30°C and 75°C (factory set to 65).

The very same KF sensor protects the boiler against overheating. It opens the mixing valve and activates the pump, if the temperature 

of boiler exceeds 95°C. In this way it prevents deactivation of thermal fuse in boiler regulation unit.

If the sensor is not connected a resistance should be used instead of it - see chapter: Installation of boiler sensor!

Under floor heating 

               from: 

to

7.2 UNDER FLOOR TEMPERATURE LIMIT: [t]

When MR-TR is used as under floor controller, maximum floor temperature can be set. Floor temperature is read by means of BF 

sensor installed in screed close to floor surface. This sensor has a function of protection.

The temperature of condense point is set between 15°C and 35°C (factory set to 29).

If the sensor is not connected a resistance should be used instead of it - see chapter Installation of boiler sensor!

CONTROLLER PARAMETER SETTING

Press 

MENU

 key to enter programme mode. The display shows parameter [n] and numeric value of ratio:

Programming is executed in three procedures. For easier understanding see the diagram on the following page.

First procedure:

 set the ratio of heating curve and parallel shift. 

Second procedure:

 set the limit of mixed flow temperature, pump deactivation, in fluence of room unit and limit of floor 

temperature or boiler condense point.

Third procedure:

 set the type of controller (radiator/under floor type heating).

When you press 

MENU

 key you enter the first procedure, where you can set the pa ram eter [n]. Change the value by pressing 

arrow keys.

To set the parameters in the second  procedure, first press 

MENU

 key and afterwards keep pressing 

E

 key for 10 sec. until parameter 

[o] is displayed, i.e. Limit of mixed flow tem pera ture.

To set the parameters in the third procedure, first press 

MENU

 key and afterwards keep pressing 

E

 key for 20 sec. until parameter 

[rAd] or [tAL] is displayed, i.e. Heating type.

When you enter the desired procedure you can change the parameter by pressing ( ) and ( ) keys. To move to the following 

parameter shortly press 

E

 key.

When the last setting of the procedure is entered, press and keep pressing 

E

 key. The display shows P.r. Keep pressing the 

E

 key 

(about 3 sec) until P.r. dis appears.

If you do not perform above stated step, all entered parameters are lost. If you do not press a key for a longer period of time during 

programming procedure, the controller leaves programming mode and returns to normal mode of operation.

When setting controller parameters for the first time, first set controller type [rAd] or [tAL] because when you change the 

type of controller factory settings are loaded.

Setting example: CONTROLLER TYPE SETTING  

2

.  [n]  value  is  dis played. 

Press 

E

 key for > 20 sec.

1

. Press 

MENU

 key.

3

. After 10 sec. value [o] is displayed, 

but keep pressing E key.

4

. Value [rAd] or [tAL] is displayed.

Set controller type with 

( ) and ( ) keys.

[rAd] - radiator heating

[tAL] - under floor heating

5

. Keep pressing 

E

 key until P.r. 

disappears and save set values.

Содержание 21128

Страница 1: ...display Code Description 21128 ROTOTERM MR TR plus Heating controller MR TR Room unit AS 2000 E sensors AF BSVF BF mounting kit 21131 ROTOTERM MR TR Heating controller MR TR sensors AF BSVF BF mounti...

Страница 2: ...t When used with radiator version the sensor is located into the boiler in order to prevent condensation or overheating of the boiler In case the boiler temperature falls bellow the condensing tempera...

Страница 3: ...5 The under floor sensor of the controller prevents the under floor to get too hot thus prevents the unpleasant feeling of warmth in your feet When used with radiator version the sensor is located in...

Страница 4: ...pins PIN CONNECTION 1 2 Put side air sensor AF 2000 3 4 Mixed flow sensor VF2000 grey colour 5 6 Room unit AS2000 5 9 6 9 7 8 Floor sensor BF2000 or boiler sensor KF2000 red colour 9 N Neutral condui...

Страница 5: ...ltage cables 2 If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V It is installed by soldering at the point where the...

Страница 6: ...se you don t have protection against floor overheating MOUNTING OF BOILER SENSOR KF 2000 for radiator heating only Mount the sensor into the cap next to the other boiler sensors In case of 4 way mixin...

Страница 7: ...ars Sensor cables shall not be placed parallel to live power supply cables as in case of electric shock there is danger of induced current which can damage the controller or room unit In case that pow...

Страница 8: ...fference Troom between actual room temperature and required room temperature When T2 BF KF key is pressed the display shows floor temperature or temperature in the boiler When T3 AF key is pressed the...

Страница 9: ...t can be modified by means of heating curve ascent or descent Range of parallel curve shift for heating curve 1 0 SELECTION OF HEATING CURVE Heating curves represent an interconnection between outside...

Страница 10: ...to This setting specifies the temperature at which the controller switches off the pump when mixing valve is already closed This function enables that all heating units are uniformly cooled down afte...

Страница 11: ...value of ratio Programming is executed in three procedures For easier understanding see the diagram on the following page First procedure set the ratio of heating curve and parallel shift Second proce...

Страница 12: ...Additionally it is equipped with room temperature display Room unit AS 2000 E has additional switch on the right side It makes possible to choose two heating regimes temperature control of mixed flow...

Страница 13: ...inutes 10 key for setting hours 11 key for setting the day of the week 12 key for input the program 13 key RESET deletes time and program 14 Slide switch for unit operation ON temperature control of m...

Страница 14: ...of operation There are two operating modes if the switch 14 in the ON position provides frost protection room temperature 8 10 C if the switch 14 in the OFF position heating is switched off closes mix...

Страница 15: ...o a lower temperature On the display appears symbol which indicates switching to higher temperature 2 First switching cycle for switching to higher temperature On display appears symbol for first sett...

Страница 16: ...xt switch cycle etc Temporary heating regime change Temporary change of regime is valid till next switch cycle When you re in automatic mode slide switch 2 in position AUTO press to change the regime...

Страница 17: ...to position AUTO program is not set See the example of program settings the program is incorrectly configured for each switch cycle to a higher temperature is followed switch cycle to a lower temperat...

Страница 18: ...T3 sensors If T2 or T3 key is pressed Er2 is displayed Sensor T2 or T3 short circuited Check T2 and T3 sensors The controller operating normally Sometimes it happens that the controller repeatedly re...

Отзывы: