background image

 

10 

 

© 2021 Carrier 

 

11.2 In case of air tube wear or damage: 

– 

if air tube or mounting ring has to be replaced - order a replacement air tube (with mounting ring) of length 
“L” – prices on request only, 

– 

if just the end of air tube is eroded by temperature - cut 200 mm of the tube tip and weld new section of the 
same length using tube SS310/330 of size 32x1.5. 
List of pilot spare parts Part Numbers is in Table 2. 

11.3 

The warranty (see page 16) covers delivered devices and materials under conditions of proper 

installation, start-up, operation and maintenance, it means the use in accordance with applicable 
instructions and manuals. 

This is particularly applicable to overheated parts i.e. working above their maximum operating 
temperature defined in Instruction Manual. 

11.4 The defective device or part will be replaced or repaired at manufacturer’s option. 

The warranty applies to and may be executed only on a failed device send to the manufacturer warehouse for 
examination or warranty repair. 

11.5 The manufacturer does not accept liability for damage to persons or property resulting 

from: 

– 

mechanical damages, 

– 

improper installation, operation, maintenance of igniter contrary to the instructions in the user manual, 

–    

unauthorized igniter modifications or repairs made by unauthorized personnel, 

– 

use of components or spare parts other than original. 

11.6 During the guarantee period any repairs must be carried out by the manufacturer service department, or the 

user, upon the service's notification and consent. 

11.7 Replacement of the consumables can be user-performed only after expiration of the guarantee. 

FIGURE 5. 

Loose Spare Parts set for SP-32 and SP-48 pilots 

Loose Spare Parts set includes: 
1 - rod gland 

1

/

2

” NPT – 1 pc\ 

 

2 - gasket OD 25x5 (for 

SP-32

) – 1 pc 

3 - O ring 46x3 (for 

SP-48

) – 1 pc 

4 - thumb screw M4 with snap ring 

(for 

SP-32-ND 

and 

SP-48-ND

) – 1 pc 

12. 

STORAGE 

SP-32 

gas pilot should be stored in a clean, dry environment and in its original packaging. 

In case of long length pilots, always keep them in a horizontal position by supporting both ends and in the middle. 
It should also be protected from contamination using caps on gas and air inlet and pilot outlet and covering with foil. 
Storage over 30 days: relative humidity of no more than 85%, temperature below 50°C. 

NOTICE

:  THE  MANUFACTURER  RESERVES  THE  RIGHT  TO  CARRY  OUT 

MODIFICATIONS TO THE PRODUCT DESCRIBED IN THIS INSTRUCTION MANUAL 

AT ANY TIME AND WITHOUT ANY ADVANCE NOTICE. 

2

3

4

Содержание SureFire II SP32-NG-FD

Страница 1: ...or LPG gas is SP 48 PG FD xxx where xxx is the insertion length L from 0 5 to 3 0 metres see Appendix 1 the pilot capacity vs gas pressure graphs for Natural gas and Propane For other Fuel gas types...

Страница 2: ...and should be ordered separately SP 32 FD pilot principle of use gas is supplied through the inlet 1 2 BSP to the gas head and to the gas tube and orifice stabilizer assembly Gas exits the main nozzle...

Страница 3: ...n left to be welded to the burner plate Pilot fixing inside the mounting tube as in p 7 1 There are two lengths A available 150 and 600 mm FIGURE 3 Gas pilot type SP 32 NG PG FD with examples of elect...

Страница 4: ...2 BSP inner thread Operating temperature max continuous 300 C orifice stabilizer end of gas and air tube 500 C Igniter rod reference length range L 0 5 3 0 m longer upon request Pilot weight P N SP 3...

Страница 5: ...S IN OPERATION ALWAYS KEEP THE PROPER AIRFLOW OF PILOT COMBUSTION COOLING AIR 7 1 MOUNTING TUBE The mounting tube if used should be attached to the burner plate using bolts or welding see Fig 2 If it...

Страница 6: ...ign of the main burner If an existing pilot has to be replaced the insertion length and pilot tip position should be the same In case of any doubts the position of the pilot should be consulted with t...

Страница 7: ...the air tube may start to glow it starts to glow at 400 500 C as the main flame burns inside the igniter Further opening of the air valve should stabilize the flame outside the air tube This will sto...

Страница 8: ...absence of the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of seq...

Страница 9: ...ilot does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c The prese...

Страница 10: ...allation operation maintenance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts...

Страница 11: ...Natural Gas or Propane Gas Forced Draught 3 0 m insertion length The Table 2 below shows Part Numbers of gas igniter mounting tubes and spare parts Table 2 SureFire II Pilot Mounting Tubes Spare Part...

Страница 12: ...12 2021 Carrier APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Страница 13: ...ndustrial heaters shows position of SP 32 and SP 48 Gas Igniter operating as a continuous pilot on a sample main burner with gas spuds and central oil or gas gun vertical mounting The pilot air tube t...

Страница 14: ...biogas and especially refinery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas...

Страница 15: ...35 315 cubic foot ft3 Air flow rate 1 cubic meter hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig...

Страница 16: ...ls which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRAN...

Отзывы: