It should be remembered that the rod tip positioning against the stabilizer plate in the pilot gas part  assembly 
(pos. 3 on Fig.1) should be done outside the air tube only. 
Only after proper rod positioning should the rod be fixed by tightening the gland and the whole gas assembly 
with rod inserted into the air tube. 

b)

 

Mounting of electrical igniter rod in a pilot: unscrew the rod tip, disassemble the gland, put all gland 
parts on rod, insert the rod in gas head, screw back the rod tip and then set the appropriate tip position 
relative to an orifice-stabilizer assy. Now the gland can be screwed onto gas head tightly. 

In case of 

problems in sliding the rod through rings of fixing gland apply a small amount of high temperature resistant 
grease or grind slightly the gland ring inner surface. 
After setting the correct rod position, fasten the rod fixing gland in the gas head. Then the complete gas part 
assembly can be slid into the air tube. 
Do not remove the rod from fixing gland if it is not necessary as the gland rings once clamped on rod do  not 
allow easy rod movement. 
After setting the correct rod position, fasten the rod fixing gland in the gas head. Then the complete gas part 
assembly can be slid into the air tube. 

c)

 

Gas part assembly and air tube should be fastened by the mounting ring thread joint. Ensure that the ring 
gasket is correctly fitted in the gas head seat (see Fig. 4). 

d)

 

The complete pilot (air tube) can be inserted into the mounting tube. In order to make the air tube slide-in 
easier, apply a small amount of high temperature resistant grease. 

e)

 

The insertion depth of 

SP-32-FD 

pilot is determined by the design of the main burner. 

If an existing pilot has to be replaced, the insertion length and pilot tip position should be the same. 
In case of any doubts, the position of the pilot should be consulted with the pilot or burner manufacturer. 

f)

 

After  determining  the  position  of  the  complete  pilot  relative  to  the  mounting  tube,  the  mounting  tube 
clamping screws should be tightened to prevent the device from moving. 

FIGURE 4. 

Gas head with ring gasket and orifice-stabilizer assembly 

7.3 GAS AND AIR SUPPLY INSTALLATION 

a)

 

The pilot must be set in the mounting tube such that the air and gas connections are in the desired position. 

b)

 

Connect the air and gas hoses to the appropriate pilot inputs. Hoses cannot be tangled or twisted. If necessary, 
additional connectors may be used. 

c)

 

To ensure a long and trouble-free operation of the pilot it should be kept clean. Check the condition of the 
gas pipe and if the orifices are not blocked. Remove all buildups. Hoses should be dry and not cracked. 

d)

 

During service works, secure the disconnected ends of the hoses by closing the ends with a plug or a tape. 

e)

 

Use the automatic shutoff valves of the appropriate size and the respective closing rate and pilot gas pressure 
measurement with safety interlocks (compliant with the requirements of relevant standards concerning the 
shut-off safety fuel valves and burner safety) to be sure that the gas delivered to the pilot is of an adequate 
pressure and can be quickly and effectively shut off. 

f)

 

Use manual shut-off valves on air and gas lines for each pilot in case of maintenance or replacement and for 
adjustment of pressure and flow on each pilot separately. 

7.4 CABLING 

Wiring and electrical connections design and layout should be in accordance with the requirements for burner 
installation devices specified in their instructions and the relevant regulations.

 

 

Содержание SureFire II SP32-NG-FD

Страница 1: ...or LPG gas is SP 48 PG FD xxx where xxx is the insertion length L from 0 5 to 3 0 metres see Appendix 1 the pilot capacity vs gas pressure graphs for Natural gas and Propane For other Fuel gas types...

Страница 2: ...and should be ordered separately SP 32 FD pilot principle of use gas is supplied through the inlet 1 2 BSP to the gas head and to the gas tube and orifice stabilizer assembly Gas exits the main nozzle...

Страница 3: ...n left to be welded to the burner plate Pilot fixing inside the mounting tube as in p 7 1 There are two lengths A available 150 and 600 mm FIGURE 3 Gas pilot type SP 32 NG PG FD with examples of elect...

Страница 4: ...2 BSP inner thread Operating temperature max continuous 300 C orifice stabilizer end of gas and air tube 500 C Igniter rod reference length range L 0 5 3 0 m longer upon request Pilot weight P N SP 3...

Страница 5: ...S IN OPERATION ALWAYS KEEP THE PROPER AIRFLOW OF PILOT COMBUSTION COOLING AIR 7 1 MOUNTING TUBE The mounting tube if used should be attached to the burner plate using bolts or welding see Fig 2 If it...

Страница 6: ...ign of the main burner If an existing pilot has to be replaced the insertion length and pilot tip position should be the same In case of any doubts the position of the pilot should be consulted with t...

Страница 7: ...the air tube may start to glow it starts to glow at 400 500 C as the main flame burns inside the igniter Further opening of the air valve should stabilize the flame outside the air tube This will sto...

Страница 8: ...absence of the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of seq...

Страница 9: ...ilot does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c The prese...

Страница 10: ...allation operation maintenance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts...

Страница 11: ...Natural Gas or Propane Gas Forced Draught 3 0 m insertion length The Table 2 below shows Part Numbers of gas igniter mounting tubes and spare parts Table 2 SureFire II Pilot Mounting Tubes Spare Part...

Страница 12: ...12 2021 Carrier APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Страница 13: ...ndustrial heaters shows position of SP 32 and SP 48 Gas Igniter operating as a continuous pilot on a sample main burner with gas spuds and central oil or gas gun vertical mounting The pilot air tube t...

Страница 14: ...biogas and especially refinery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas...

Страница 15: ...35 315 cubic foot ft3 Air flow rate 1 cubic meter hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig...

Страница 16: ...ls which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRAN...

Отзывы: