APPLICATION
•
For single or dual fired burners, pilot ignited or direct ignited continuous duty.
•
One basic model meets various European standards.
•
ED510 message center indicating in English, French, Dutch, Spanish, or German program
sequence and reasons for alarm burner shutdown
•
A constant flame signal read-out via ED510 message center.
•
Read-out of main fuel operation hours, burner cycles, total number of safety shutdowns, and the
reason for the last six safety shutdowns via the ED510 message center.
•
A run/check switch which allows the operator to stop the program sequence in any of three dif-
ferent positions (Purge, PTFI, or Auto).
•
Selectable purge timings
•
Different detection methods for the Flame-Monitor control are:
— infrared
— ultra-violet
— ultra-violet self-check
— flame rectification
with a correspondingly large choice of flame scanner constructions.
DESIGN FEATURES
•
Microprocessor based technology.
•
Plug-in control unit with “snap-on” protection cover.
•
“Burnt-in” electronic circuits eliminating aging and temperature problems.
•
Gold-plated plug-in contact fingers
•
Accurate timings; watchdog timer to supervise ignition and travel time of modulator motor
•
Overload and short-circuit protection
•
Built-in self-diagnostic
SPECIFICATIONS
Humidity:
85% RH maximum (non-condensing).
All components epoxy coating sealed.
Operating temperature limits:
CHASSIS
TEMPERATURE
Max.
Min.
EB720
60°C
- 20°C *
EB721
60°C
- 20°C *
Amplifiers, Programmer
60°C
- 20°C *
ED510 Message Center
60°C
0°C *
All UV scanners
100°C
- 20°C *
All infrared scanners
52°C
- 20°C *
* Unit tested down to -20 °C. Minimum operating characteristics, subject to supply voltage changes