18
Press the Mode key and the screen displays:
E320 TERM #22
LOW OIL TEMPERATURE
or programmed message.
Press the Scroll key and the screen displays:
E320 TERM #24
LOW OIL PRESSURE
or programmed message.
To change the message, press and hold the Reset key for one (1) second. When the Reset key is
released, the screen displays:
MDFY TERM #24
LOW OIL PRESSURE
Press the Scroll key to display the available messages for the particular group being modified. See
attached List of available messages for each group.
When the messages displayed is appropriate for the terminals, press and hold the Reset key for one
(1) second. When the Reset key is released, the screen displays:
E320 TERM #24
.
HIGH OIL PRESSURE
or programmed message.
Press the Mode key to exit the E320 Message Sub-menu.
AVAILABLE E320 MESSAGES
The following messages are available for each of the four E320 terminal groups:
GROUP 1 – OIL SELECT
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
HIGH OIL PRESSURE
LOW OIL TERMPERATURE
LOW ATOMIZING TEMPERATURE
AUX OIL
GROUP 2 – GAS SELECT
HIGH GAS PRESSURE
AUX GAS
LOW GAS PRESSURE
GROUP 3 – NON-RECYCLE
E340 SAFETY INTLK OPEN
HIGH TEMPERATURE
HIGH WATER
AIR FLOW OPEN
LOW WATER
OIL GUN END SWITCH OPEN
HIGH PRESSURE
HIGH STACK TEMPERATURE
F.D. FAN INTLK
BLOWER MOTOR INTLK
I.D. FAN INTLK
AUX NR1
COMBUSTION AIR FLOW FAILURE
AUX NR2
AUX NR3