16
HISTORICAL INFORMATION /SYSTEM SUB-MENUS
At any time the control is powered, the SCRL key will scroll through and display the total number of
burner cycles, burner lockouts, and system hours on the bottom line of the ED510 display. The top
line will continue to show the current run mode of the control (e.g. PURGE, AUTO, etc.). Following
the historical information, the SCRL key will display four (4) System Sub-menus providing the fol-
lowing information and/or functions:
— Lockout History (with burner cycle and burner hour time stamp).
— E320 Message Select (to program messages associated with the E320 Expansion Module.
— Program Setup (to display programmer type, purge timing, FFRT timing, etc.).
— System Information (status of M-D circuit, average pilot flame signal, etc.).
The system sub-menus require the MODE key to gain access to the information associated with each
sub-menu. An arrow is displayed in the lower right hand corner of the display to indicate a system
sub-menu. Every time the SCRL key is pressed the information is displayed as follows:
Number of burner operating cycles. (L1-3 closed).
Number of burner lockouts.
Number of hours the control has been powered.
Sub-menu to display the cause of the last 6 lockouts. The MODE key is required to
display the actual lockouts.
Sub-menu to program the messages associated with the operation of the E320
expansion module. The MODE key is required to enter the sub-menu.
Sub-menu to display various operating parameters of the programmer and ampli-
fier. The MODE key is required to enter the sub-menu.
Sub-menu to display information pertaining to the operation of the control. The
MODE key is required to enter the sub-menu.
AUTO
40
BNR CYCLES
385
AUTO
40
BNR LOCKOUTS
21
AUTO
40
SYS HOURS
233
AUTO
40
ALARM HISTORY
>
AUTO
40
E320 MSG SELECT
>
AUTO
40
PROGRAM SETUP
>
AUTO
40
SYSTEM INFO
>