6
ACCESSORIES AND SPARE PARTS
DIPSWITCHES FOR SELECTABLE OPERATION
Several operational characteristics of the EP113 programmer modules are determined by six (6)
dipswitches located on the side of the programmer. These characteristics include non-recycle/recycle
operation when the running interlock circuit (3-P) is opened (Dipswitch #1), interrupted or intermit-
tent operation of terminal 5 (Dipswitch #2), extended purge timing (Dipswitches #3, #4, #5), and
enable or disable the option that requires the 3-P running interlock circuit to be proven open at the
start of the operating cycle (Dipswitch #6).
WARNING: THE INAPPROPRIATE SELECTION OR APPLICATION OF A PROGRAM-
MER MODULE COULD RESULT IN AN UNSAFE CONDITION HAZARDOUS TO LIFE
AND PROPERTY. Changing the dipswitches modifies the operation of each programmer
module. Care should be taken to insure the proper dipswitch settings. Setting the dipswitches
for a particular application should be made by a competent professional, such as a Boiler/
Burner technician licensed by a state or other government agency, engineering personnel of
the burner, boiler, or furnace manufacturer (OEM) or in performance of duties based on
information from the OEM.
DESCRIPTION
TYPE
FOR
Firetron cell
4-263-1
48PT2
UV tube
4-314
45UV3, 45UV5
Lens
61-436
48PT2
Quartz lens (3/4”)
46-56
45UV3
Quartz lens (1”)
46-38
45UV5
Union coupling
– with glass lens
– with quartz glass
– with quartz lens
60-801
60-1257
60-1290
48PT2
UV1A
UV1A
Heat insulator (1/2" NPT)
35-69
48PT2/UV1A
Heat insulator (1" BSP)
35-127-3
45UV5
Heat insulator (1" NPT)
35-127-1
45UV5
Swivel mount (1/2" NPT)
60-302
48PT2/UV1A
Swivel mount (1" BSP)
60-1664-4
45UV5
Swivel mount (1" NPT)
60-1664-3
45UV5
UP
DOWN
PRINTED CIRCUIT BOARD
DIPSWITCH POSITION #1
FRONT COVER