ACCESSORIES AND SPARE PARTS

DIPSWITCHES FOR SELECTABLE OPERATION

Several operational characteristics of the EP113 programmer modules are determined by six (6)
dipswitches located on the side of the programmer. These characteristics include non-recycle/recycle
operation when the running interlock circuit (3-P) is opened (Dipswitch #1), interrupted or intermit-
tent operation of terminal 5 (Dipswitch #2), extended purge timing (Dipswitches #3, #4, #5), and
enable or disable the option that requires the 3-P running interlock circuit to be proven open at the
start of the operating cycle (Dipswitch #6).

WARNING: THE INAPPROPRIATE SELECTION OR APPLICATION OF A PROGRAM-
MER MODULE COULD RESULT IN AN UNSAFE CONDITION HAZARDOUS TO LIFE
AND PROPERTY. Changing the dipswitches modifies the operation of each programmer
module. Care should be taken to insure the proper dipswitch settings. Setting the dipswitches
for a particular application should be made by a competent professional, such as a Boiler/
Burner technician licensed by a state or other government agency, engineering personnel of
the burner, boiler, or furnace manufacturer (OEM) or in performance of duties based on
information from the OEM.

DESCRIPTION

TYPE

FOR

Firetron cell

4-263-1

48PT2

UV tube

4-314

45UV3, 45UV5

Lens

61-436

48PT2

Quartz lens (3/4”)

46-56

45UV3

Quartz lens (1”)

46-38

45UV5

Union coupling

– with glass lens
– with quartz glass
– with quartz lens

60-801
60-1257
60-1290

48PT2
UV1A
UV1A

Heat insulator (1/2" NPT)

35-69

48PT2/UV1A

Heat insulator (1" BSP)

35-127-3

45UV5

Heat insulator (1" NPT) 

35-127-1

45UV5

Swivel mount (1/2" NPT)

60-302

48PT2/UV1A

Swivel mount (1" BSP)

60-1664-4

45UV5

Swivel mount (1" NPT)

60-1664-3

45UV5

 

UP

DOWN

PRINTED CIRCUIT BOARD

DIPSWITCH POSITION #1

FRONT COVER

Содержание FLAME-MONITOR E210

Страница 1: ...ssage indicating the cause Interchangeable flame amplifier and program mer modules allow for complete versatility in the selection of flame detectors and display language English French Dutch German S...

Страница 2: ...r control are infrared ultra violet ultra violet self check flame rectification with a correspondingly large choice of flame scanner constructions DESIGN FEATURES Microprocessor based technology Plug...

Страница 3: ...minal 6 5s Post purge 10 s becomes 20 s in case of flame or ignition failure Flame failure response time Maximum 1 s for EP113 Note Flame failure response time for the EP113 is 1 5 seconds when used w...

Страница 4: ...EQUIRED E1R3 EUV1 EUVS4 60 1386 2 60 1466 2 PROGRAMMER MODULE ONE REQUIRED EP PROGRAMMER E210 CONSISTS OF EB720 EC600 48 1836 SURFACE MOUNT SHOWN CABINET MOUNT E211 CONSISTS OF EB721 EC600 48 1836 CHA...

Страница 5: ...E SCANNERS INFRARED Type Cable Length Version Mounting 48PT2 1003 2400 mm Straight head 1 2 NPT 48PT2 1007 1200 mm Straight head 1 2 NPT 48PT2 9003 2400 mm 90 head 1 2 NPT 48PT2 9007 1200 mm 90 head 1...

Страница 6: ...fies the operation of each programmer module Care should be taken to insure the proper dipswitch settings Setting the dipswitches for a particular application should be made by a competent professiona...

Страница 7: ...he high fire switch is proven closed term D 8 At the end of the purge timing the firing rate motor is driven to the low fire position 10 12 and waits until the low fire start interlock is proven close...

Страница 8: ...plugs into the RJ45 style connectors on both the ED510 display and programmer module Check Run Switch The Check Run switch is located on the top of the EP113 Programmer Module Engineering code 21 or h...

Страница 9: ...include the thermostat switch which is closed when heat is required 2 Running interlocks 3 P If any interlock switch in this circuit opens all open fuel valves will be closed immediately and the cont...

Страница 10: ...message center will provide a readout of the signal strength both during pilot proving time and main burner operation 9 Following a 10 second proved pilot stabilization period the main fuel valve term...

Страница 11: ...an 1 second During prepurge Opening of non recycling interlocks 3 P False flame sensed Dipswitch 6 enables or disables this requirement See Dipswitches for Selectable Operation TERMINAL LOAD M X 5 6 7...

Страница 12: ...e the control instead of going into alarm See Dipswitches for Selectable Opera tion 10 PV MV S2 11 M 7 12 13 X 5 6 D A 3 P S1 L1 L L2 N MODULATOR PILOT VALVE MAIN VALVE IGNITION TRANSFORMER HIGH LOW A...

Страница 13: ...iting maximum 180 seconds for the modulator to run to the LOW position waiting for the low fire circuit M D to close 10 second mini mum Unsupervised pilot trial for ignition time maximum 5 seconds Pil...

Страница 14: ...ing burner operation Alarm messages related to the IGNITION and FLAME FAILURE These messages scroll on the display when the control and scanner fail to prove the presence of flame After the post purge...

Страница 15: ...ing driven to the low fire position The Run Check switch has been placed in the Check position during the pilot trial for ignition period Flame signal strength is displayed in the upper right hand pos...

Страница 16: ...ess to the information associated with each sub menu An arrow is displayed in the lower right hand corner of the display to indicate a system sub menu Every time the SCRL key is pressed the informatio...

Страница 17: ...imits connected between terminals 3 and P of the E210 E211 control These are terminals 29 30 31 32 33 34 and 35 The lockout messages associated with the above terminals can be modified via the ED510 D...

Страница 18: ...ls press and hold the Reset key for one 1 second When the Reset key is released the screen displays E320 TERM 24 HIGH OIL PRESSURE or programmed message Press the Mode key to exit the E320 Message Sub...

Страница 19: ...PROGRAM SETUP Setup is displayed Control has released to auto modulation flame signal strength 45 MODE AUTO 45 Programmer Type is an EP113 PROGRAMMER EP113 SCRL AUTO 45 Software Engineering code of th...

Страница 20: ...ation until SYSTEM INFO System Info is displayed Control has released to auto modula tion flame signal strength 45 SCRL AUTO 45 The average flame signal strength of the pilot flame 22 AVG PILOT FLM 22...

Страница 21: ...ff and can be snapped back into place easily INSTALLING AMPLIFIER MODULE The flame amplifier module is installed in the third set of guide channels found in the EB720 and EB721 FLAME MONITOR chassis I...

Страница 22: ...LECTRIC POWER MUST BE TURNED OFF DURING INSTALLATION FIELD WIRING The use of 2 5mm2 wires rated at 600V is appropriate for all field wiring The wiring base is pro vided with eighteen 18 numbered termi...

Страница 23: ...ack to the scanner The maximum UV signal from a flame is found in the first one third of the visible flame taken from the point where the flame begins The scanner sight pipe should be aimed at this ar...

Страница 24: ...ire Infrared scanner wiring Infrared scanner type 48PT2 is provided with a flexible conduit The two wires are to be connected to a coaxial cable via a junction box Maximum cable length between scanner...

Страница 25: ...69 ALTERNATE STANDARD MOUNTING NOT ADJUSTABLE 1 2 SIGHT PIPE UV1B 6 50 50 50 15 50 35 127 HEAT INSULATING NIPPLE AIR ENTRY MOUNTING FOR SPECIAL APPLICATIONS 1 SWIVEL MOUNT 60 1664 AND COOLING AIR ENTR...

Страница 26: ...ns The ultraviolet detector is ideally suited to all gas burners or combination gas oil burners The area to scan with an ultra violet detector is within the first 1 3 length of the flame since this is...

Страница 27: ...vation of the flame signal strength on the display will forewarn of any deterioration in the capability of the flame detector or its application Contacts There are no accessible contacts in the Fireye...

Страница 28: ...61 9 UV8A SCANNER 2 53 64 3mm 2 1 4 57 2mm 700 DIA FITTING 17 8mm FOR WATER TIGHT CONDUIT SHIELDING OF 6 FT 1830mm LEADS IS REQUIRED 1 2 x 14ST PIPE THREAD 1 IN DIA 25 4mm 1 1 2 38 1mm UV1A3 3 FT TC...

Страница 29: ...29...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND...

Отзывы: