Document #51003 Rev.E 01/11/02 P/N 51003:E
81
NFPA Standard-Specific Requirements
NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Cut Jumper JP4 on the MS-9200 main circuit board to supervise placement of the RTM-8F module.
2.
Refer to Figure 2-7, “Typical UL Power-limited Wiring Requirements,” on page 27, and “UL Power-limited
Wiring Requirements” on page 27, for information on UL Power-limited wiring requirements.
Fire•Lite RS82 Remote Station Receiver UL listed.
Refer to Fire•Lite Alarms, Inc., Instruction Manual for
Remote Station Receiver Model RS82.
+ -
Polarity Shown is
Normal Standby
RTM-8F Relay
Transmitter
Module
(not suitable for
transmission of
separate alarm and
trouble signals to
Remote Station)
Cut JP1
Jumper JP2 must be in position
ALARM/TROUBLE REVERSE
POLARITY
for use in alarm and
trouble transmission or
ALARM
ONLY
for alarm transmission only
JP2 Jumper Settings:
Alarm/Trouble Polarity
Reversal Remote Station
Alarm only Polarity
Reversal Remote Station
+
-
Power-limited
FIGURE E-4:
Remote Station Connection Using RTM-8F Module