Fire-Lite MS-9200C Скачать руководство пользователя страница 3

LimWarLg.p65    01/10/2000

WARNING 

Several different sources of power can be con-

nected to the fire alarm control panel.  Disconnect all sources
of power before servicing.  Control unit and associated equip-
ment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.

CAUTION - 

System Reacceptance Test after Software

Changes.  To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific soft-
ware.  Reacceptance testing is required after any change, ad-
dition or deletion of system components, or after any modifica-
tion, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 de-
vices, must also be tested and proper system operation veri-
fied.

This system  

meets NFPA requirements for operation at

0-49° C/32-120° F

 

 and at a relative humidity of 85% RH (non-

condensing) at 30°

 

C/86° F.  However, the useful life of the

system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity.  Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nomi-
nal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate

 for all initiating and

indicating device loops.  Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices,

 this system may

operate erratically or can be damaged when subjected to light-
ning-induced transients.  Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.  

Overhead or outside

aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes.  Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.

Disconnect AC power and batteries

 prior to removing or in-

serting circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing,

reaming, or punching of the enclosure.  When possible, make
all cable entries from the sides or rear.  Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.

Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.

Though designed to last many years, 

system components

can fail at any time.  This system contains static-sensitive
components.  Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are re-
moved from the body.  Use static-suppressive packaging
to protect electronic assemblies removed from the unit.

Follow the instructions

 in the installation, operating, and

programming manuals.  These instructions must be followed
to avoid damage to the control panel and associated
equipment.  FACP operation and reliability depend upon
proper installation by authorized personnel.

Adherence to the following will aid in problem-free
installation with long-term reliability:

WARNING:

 This equipment generates, uses, and can

radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications.  It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment.  Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.

FCC Warning

Installation Precautions

Содержание MS-9200C

Страница 1: ...Addressable Fire Alarm Control Panel MS 9200 C MS 9200E E Document 51003 01 11 02 Rev 2002 Fire Lite PN 51003 E ECN 02 014...

Страница 2: ...plosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined...

Страница 3: ...anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling...

Страница 4: ...4 Document 51003 Rev E 01 11 02 P N 51003 E Notes...

Страница 5: ...nnections 25 2 2 2 Battery Power 25 2 2 3 DC Power Output Connections 25 2 3 Standard Relays 26 2 4 Notification Appliance Circuits 26 2 5 Annunciator and PC Printer Circuits 26 2 6 UL Power limited W...

Страница 6: ...ons Real Time Clock 57 4 11 Coded Operation NAC 1 and NAC 2 57 4 12 Presignal 57 4 13 Special System Timers 57 4 13 1 Silence Inhibit Timer None or 60 Seconds 57 4 13 2 Auto silence Timer None or 10 M...

Страница 7: ...Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems...

Страница 8: ...rinter OUT IN OUT IN TB3 Relays TROUBLE C NC NO ALARM C NC NO SUPV C NO J17 Xformer 1 High Voltage J19 Optional Xformer 2 High Voltage TB8 AC EARTH NEUTRAL HOT JP1 Battery Charger Disable Cut to disab...

Страница 9: ...requirements 198 addressable device capacity 99 detectors and 99 monitor control modules 56 software zones Two main circuit board NACs Notification bell Appliance Circuits expandable via control modu...

Страница 10: ...th Thermal Sensor D350P R addressable Photoelectric Duct Detector R alarm relay option B501BH B501BHT Sounder Base BB224RB Relay Base BB224BI Isolator Base MMF 300 Monitor Module MDF 300 Dual Monitor...

Страница 11: ...24 VDC Current for all external devices 3 0 amps expandable to 6 0 amps1 Current limit Fuseless electronic power limited circuitry Maximum signaling current per circuit 2 50 amps End of line resistor...

Страница 12: ...nd Fault yellow located on bottom of main circuit board refer to figure on page 8 Membrane Panel Mounted on the main circuit board the membrane switch panel includes a window for the LCD display and f...

Страница 13: ...plug in and are mounted to the main circuit board The circuit board is delivered premounted in the MS 9200 cabinet Note that newer versions of the circuit board have jumper JP1 which can be cut to di...

Страница 14: ...ite Device Compatibility Document for a list of approved detectors Smoke Detectors Photoelectric The SD350 is an intelligent addressable low profile photoelectric smoke detector which provides smoke s...

Страница 15: ...ssable control module used to connect NACs Notification Appliance Circuits to power and supervise compatible UL listed notification appliances The NACs can be wired to the module as supervised NFPA St...

Страница 16: ...circuit board When the module is installed jumper JP4 must be cut in order to provide module placement supervision The RTM 8F provides eight high current 5 amps Form C relays These relays track softwa...

Страница 17: ...r to Figure 2 11 UDACT F Mounting to MS 9200 on page 30 and Figure 2 12 External UDACT F Mounting in ABS 8RF on page 31 for wiring details and System Edit on page 45 for information on programming the...

Страница 18: ...versions of the MS 9200 main circuit board which allows disabling of the FACP battery charger The batteries and charger can be housed in the Fire Lite BB 55F Battery Box which can be mounted up to 20...

Страница 19: ...ISABLE TRANSFORMER 1 TRANSFORMER 2 BATTERY RS 232 PC PRINTER RS 485 TERM MODE TROUBLE B A A B B A A B NO C NO NC C NO NC C A B B A B A 1 COMM 2 ACS SHIELD SLC SLC OUT IN OUT IN T B 4 T B 2 T B 1 T B 3...

Страница 20: ...added to an AFM 16ATX AFM 16ATF The Annunciator Fixed Module 16ATF contains 16 red alarm and 16 yellow trouble LEDs a System Trouble LED an On Line Power LED and a local piezo sounder with switches fo...

Страница 21: ...h functions Refer to the LDM Series Lamp Drive Modules Manual for a complete description See ACS and LDM Series Wiring on page 73 for wiring requirements and System Edit on page 45 for details on prog...

Страница 22: ...ol Input 2 controls output circuits 3 and 4 During the inactive state the remote power supply supervises its NAC field wiring for short and open circuits If a fault is detected the supply will enter a...

Страница 23: ...e the top of the cabinet approximately 5 feet 1 5 m above the floor with the hinge mounting on the left Determine the number of conductors required for the devices to be installed Sufficient knockouts...

Страница 24: ...eyholes mount the backbox over the two screws 5 Mark and drill the lower two holes 6 Secure backbox by installing the remaining fasteners Tighten all screws 7 When the location is dry and free of cons...

Страница 25: ...ning the control panel s immunity to unwanted transients generated by lightning and electrostatic discharge 2 2 2 Battery Power Observe polarity when connecting the battery Connect the battery cable t...

Страница 26: ...stem information Note that the TB7 Out and In polarities are used for connection to a Terminal Mode annunciator Refer to page 35 for information on PC Printer wiring FIGURE 2 4 Relay Connections 1 2 3...

Страница 27: ...O FIGURE 2 7 Typical UL Power limited Wiring Requirements Power limited Circuits Power limited Circuits Nonpower limited Circuits Power limited Circuits Nonpower limited Circuits AC Power Note Output...

Страница 28: ...able detectors and an additional combination of up to 99 addressable pull stations control modules and monitor modules Note Refer to the installation drawings supplied with each loop device for rating...

Страница 29: ...isted in the Fire Lite Device Compatibility Document 2 8 1 UDACT F Universal Digital Alarm Communicator Transmitter The UDACT F transmits system status to UL listed Central Station receivers via the p...

Страница 30: ...T F Mounting to MS 9200 on page 30 Using the ribbon cable supplied with the UDACT F connect J10 on the UDACT F to J16 on the MS 9200 Note that the colored edge of the ribbon cable must be oriented tow...

Страница 31: ...und strap supplied with ABS 8RF enclosure from Earth Ground terminal on the UDACT F to a solid building earth ground Conduit alone will not provide a reliable earth ground 7 UDACT F may be located up...

Страница 32: ...F E Up to 32 ACM 8RF Relay Control Modules may be placed onto the EIA 485 communication bus if no other devices are installed on the bus Removable terminal blocks are provided for ease of wiring insta...

Страница 33: ...cks in place on the standoffs Be certain to tighten the screw into the metal standoff on the lower right corner This is critical to the RTM 8F transient protection Affix the terminal identification la...

Страница 34: ...To prevent the yellow Trouble LED from turning on when the Transmitter Output is not used no connec tions move jumper JP2 to the Local Energy Municipal Box position bottom two pins and install a dummy...

Страница 35: ...onnector cable P N 75267 as shown in Figure 2 17 and a DB25 adapter Connect the interface cable to TB7 on the MS 9200 main circuit board and the attached cable to the serial EIA 232 port on the printe...

Страница 36: ...ling or removing any modules or wiring Programming Refer to System Edit on page 45 for printer programming instructions Installation Older circuit boards require the PIM 24 which includes the Printer...

Страница 37: ...be ordered for this purpose When a programmed system is normal with no active alarms troubles or supervisories the SYSTEMS ALL NORMAL screen will be displayed as shown below In order to 1 program the...

Страница 38: ...ing RD BAT allows the user to read the battery voltage The RD BAT feature is NOT password protected The following screen is displayed upon entering RD BAT Initial Power up describes initial programmin...

Страница 39: ...hich will access two different screens as indicated in the preceding section From either of the screens access to specific system and device programming may be obtained All programming entries are sto...

Страница 40: ...ired to the SLC loop The panel communicates with each individual addressable device and displays the type of device at each address location starting with detectors and then modules While autoprogramm...

Страница 41: ...numeric key Custom words may be entered via the keypad The alphanumeric operation of the keypad changes a blinking letter in the ADJ and NOUN fields For example to enter the letter R repeatedly press...

Страница 42: ...ve increment function may be repeated with each press of the Zero key As an example the user could quickly enter FLR_3_ROOM_305 as follows 1 The cursor is on the first letter of the ADJ field Press th...

Страница 43: ...reen above Note that selection of a type code may change the functional operation of the addressable device Follow the same procedure as described in New Detectors section for editing of the ADJ and N...

Страница 44: ...an alarm condition The following display will appear For example select Detector address 3 program edit by pressing key detector followed by numeric key 3 followed by ENTER Select Module address 3 pro...

Страница 45: ...e Y 73 seconds SI Silence Inhibit N one Y 60 seconds1 AS Autosilence N one Y 10 minutes1 PS Presignal N one Y 3 minutes with 15 second Acknowledge1 CD Bell Code 1 M arch Time N one No Coding steady No...

Страница 46: ...nchanged and the program returns to the program change screen FUNCTION DEFAULT SELECTION V Alarm Verification N one Y 73 seconds I Silence Inhibit N one Y 60 seconds1 A Autosilence N one Y 10 minutes1...

Страница 47: ...een will be displayed The left arrow key may be used to return to the program change screen The PC connects to the EIA 232 printer interface instructions provided with the Upload Download software kit...

Страница 48: ...abel ENABLE blinking The current status label may show NORMAL TROUBL DISABL ALARM ACTIVE PROGRM TEST 01 ON OFF The status label can be changed to DISABL or back to its present status by pressing the u...

Страница 49: ...0 event history buffer After pressing either 1 or 2 the screen shown below will appear If ENTER is pressed the second line goes blank and the unit is in Walktest mode Walktest may be stopped at any ti...

Страница 50: ...t activated The LCD displays the following 3 4 4 Set Time and Date If 4 is pressed the following is displayed The first digit of the hours is flashing and may be changed with the numeric pad The right...

Страница 51: ...turn on It also sends an Alarm Silenced message to the printer the history file and the LCD 40 A subsequent new alarm will resound the system 4 1 3 Drill Hold 2 Sec When the Drill key is held for two...

Страница 52: ...ce key is pressed preceded by a fire alarm condition It turns off when the Drill or System Reset key is pressed System Trouble This is a yellow LED that flashes when one or more trouble conditions occ...

Страница 53: ...DET indicates smoke detector Point type and address in this example P01 indicates Photoelectric detector assigned to address 01 The information displayed in the second line in the example above provi...

Страница 54: ...ts active in the system block acknowl edge When the Acknowledge Step key is pressed and at least one new alarm or trouble exists in the system the Acknowledge message is sent to the printer and histor...

Страница 55: ...played Alarms latch and are not allowed to clear automatically Alarms activate software zones control by event logic if so programmed Timers Silence Inhibit Autosilence Trouble Reminder are started Al...

Страница 56: ...device control module or NAC that is not disabled is turned on when any of the software zones to which it is mapped become active 4 9 Detector Functions Maintenance Alert Each detector is monitored by...

Страница 57: ...iezo is silenced and the notification appliances will not activate for up to three minutes After three minutes the NACs will activate if the source of the alarm is not cleared This does not affect mon...

Страница 58: ...WV ZKLFK DUH GLVDEOHG GR QRW FDXVH DQ DODUP RU DQ RQWURO YHQW DFWLYLW LVDEOHG RXWSXW SRLQWV DUH KHOG LQ WKH RII VWDWH OO GLVDEOHG SRLQWV DUH WUHDWHG DV LI WKH ZHUH LQ WURXEOH ZLWK WKH H FHSWLRQ EHLQJ...

Страница 59: ...all subsequent operations except print operations a two minute timer is started that will cause the panel to return to the previous display if no key is pressed within two minutes Each key press resta...

Страница 60: ...history file may be printed using the Print History feature by pressing 2 while viewing the Print screen Refer to Printer PC and Terminal Mode Annunciator Interface on page 35 for instructions on con...

Страница 61: ...re must run continuously without any disconnect devices from the power source to the fire alarm control panel Overcurrent protection for this circuit must comply with Article 760 of the National Elect...

Страница 62: ...to Current Limitations on following page 7 During AC loss the LCD 40 backlight is extinguished to conserve power reducing the standby current draw from the batteries to 0 029 amps 8 Maximum alarm curr...

Страница 63: ...Board 1 X 0 168 0 168 RTM 8F one max X 0 1462 2 All RTM 8F Relays activated ACM 8RF X 0 1583 3 All eight ACM 8RF Relays activated on a single module ACM 16ATF ACM 32AF one max X 0 0564 4 All annuncia...

Страница 64: ...of FACP battery charger by cutting JP1 the CHG 120F Battery Charger for 25 AH to 100 AH batteries requires separate housing TABLE A 4 Battery Calculations Standby Load Current amps X Required Standby...

Страница 65: ...ximum of 99 addressable output devices Use the charts on the following pages to help in zoning the system Note that monitor and control modules make up one group of 99 addresses It is critical that ad...

Страница 66: ...Inputs and Outputs to Zones FIGURE B 1 Zoning Example SD350 01 SD350 02 MMF 300 01 CMF 300 05 CMF 300 04 ZONE 01 MMF 301 02 CP350 03 CP350 04 CMF 300 07 CMF 300 06 CMF 300 03 ZONE 02 SD350 05 SD350 06...

Страница 67: ...ax NOUN 9 charact max 01 SD350 1 FIRST HALL 51 02 SD350 1 ELEV LOBBY 52 03 CP350 2 2ND FLOOR 53 04 CP350 2 ROOM 210 54 05 SD350 3 3RD FLOOR 55 06 SD350 3 MEZZANINE 56 07 CP350 3 MECH ROOM 57 08 58 09...

Страница 68: ...MMF 300 1 WEST HALL 51 02 MMF 301 2 EAST STAIRWELL 52 03 CMF 300 1 2 3 2ND FLOOR 53 04 CMF 300 1 1ST FLOOR 54 05 CMF 300 1 EAST HALL 55 06 CMF 300 2 ELEV LOBBY 56 07 CMF 300 2 MEZZANINE 57 08 CMF 300...

Страница 69: ...Document 51003 Rev E 01 11 02 P N 51003 E 69 Software Zones FIGURE B 2 Blank Zoning Sheet Input Devices Zones Output Devices...

Страница 70: ...N 9 charact max Address Device Type Zone Number ADJ 5 charact max NOUN 9 charact max 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 2...

Страница 71: ...ax NOUN 9 charact max Address Device Type Zone Number ADJ 5 charact max NOUN 9 charact max 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 1...

Страница 72: ...Carefully seat the DIM 485 connector on the main circuit board J11 connector and press to seat the DIM 485 on the standoff 24V UNREG 24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV ALARM TROUBLE PC...

Страница 73: ...ch to prevent unauthorized actuation of control switches Refer to the AFM Manual for further details 24V UNREG 24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV ALARM TROUBLE PC PRINTERTERM COMM GND FA...

Страница 74: ...ystem 24V UNREG 24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV ALARM TROUBLE PC PRINTER TERM COMM B A A B B A A B NO C NO NC C NO NC C A B B A B A 1 COMM 2 ACS SHIELD SLC SLC OUT IN OUT IN T B 4 T B...

Страница 75: ...4V RST BELL 2 POWER BELL 1 POWER SUPV ALARM TROUBLE PC PRINTER TERM COMM GND FAULT DISABLE TRANSFORMER 1 TRANSFORMER 2 BATTERY RS 232 PC PRINTER RS 485 TERM MODE TROUBLE B A A B B A A B NO C NO NC C N...

Страница 76: ...BLE PC PRINTER TERM COMM GND FAULT DISABLE BATTERY RS 232 PC PRINTER RS 485 TERM MODE TROUBLE B A A B B A A B NO C NO NC C NO NC C A B B A B A 1 COMM 2 ACS SHIELD SLC SLC OUT IN OUT IN T B 4 T B 2 T B...

Страница 77: ...tected Premises Unit and Remote Station Service requires MS 5012 for connection to a compatible listed Central Station DACR or Protected Premises Receiv ing Unit This unit must be installed as outline...

Страница 78: ...the MS 5012 for slave operation 3 SW2 Trouble switch located on the bottom right of the MS 9200 main circuit board must be positioned in the down position for this application This prevents the trans...

Страница 79: ...UBLE PC PRINTER TERM COMM B A A B B A A B NO C NO NC C NO NC C A B B A B A 1 COMM 2 ACS SHIELD SLC SLC OUT IN OUT IN T B 4 T B 2 T B 1 T B 3 T B 7 T B 5 T B 6 TB2 TB1 U8 U10 U11 J1 J2 J4 PH1 R41 PH2 M...

Страница 80: ...rcuit board to supervise placement of RTM 8F module and circuit 3 Refer to Figure 2 7 Typical UL Power limited Wiring Requirements on page 27 and UL Power limited Wiring Requirements on page 27 for in...

Страница 81: ...re Lite RS82 Remote Station Receiver UL listed Refer to Fire Lite Alarms Inc Instruction Manual for Remote Station Receiver Model RS82 Polarity Shown is Normal Standby RTM 8F Relay Transmitter Module...

Страница 82: ...n Supervisory condition Form C Trouble contact which will automatically activate on any Trouble condition Form C Alarm contact programmed to activate on General Alarm MS 9200 Main Board MS 9200 Addres...

Страница 83: ...9583 WPW999 14 AWG 2 00 mm2 Genesis 4408 4608 Signal 98430 Belden 9581 WPW995 16 AWG 1 30 mm2 Genesis 4406 4606 Signal 98630 Belden 9575 WPW991 18 AWG 0 75 mm2 Genesis 4402 4602 Signal 98300 Belden 95...

Страница 84: ...ek Press 1 Disable Enable Point Press 2 Clear Event File Press 3 Walktest Press 4 Time Press 5 Program Check Disable Enable Press AA ENTER ENTER to Clear Hist Backspace to Escape Walktest 1 Silent 2 P...

Страница 85: ...Press 1 Press 2 EXAMPLE NORMAL MONITOR M01 Z V N I N A N P N C M A U M L P N S 4 R N EXAMPLE OFF SOFTWARE ZONE Z EXAMPLE OFF BELL CKT B01 PANEL CIRCUIT Z EVENT HISTORY START EVENTS IN HIST XXXX Press...

Страница 86: ...86 Document 51003 Rev E 01 11 02 P N 51003 E Notes...

Страница 87: ...ming 50 Clear History 49 Clear Programming 40 CMF 300 15 Communication Loop 11 13 Specification 11 Control By Event 56 Controls 12 51 Acknowledge Step 51 Alarm Silence 51 Drill 51 System Reset 51 CP35...

Страница 88: ...tory 60 Print Detector Data 60 Print History 60 Print Program 60 Recall Increment 42 Relay Control Module 32 Relay Transmitter Module 29 Components 34 Relays 11 13 26 32 RTM 8F 16 27 31 80 81 Installa...

Страница 89: ...Document 51003 Rev E 01 11 02 P N 51003 E 89 Notes...

Страница 90: ...90 Document 51003 Rev E 01 11 02 P N 51003 E Notes...

Страница 91: ...ansportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will pr...

Страница 92: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com...

Отзывы: