25
Obey the following instructions:
• Protect the MVCS with wooden corners, plastic film, etc. The MVCS is delivered unpacked from the factory as
standard.
• Protect the interior of the MVCS from rainwater by using temporary protection plates (anti-typhoon) on air intakes
and outlets.
• The MVCS is built to fit inside:
–
20 ft HC container → 1 MVCS
–
40 ft HC container → up to 2 MVCS (consider the maximum permissible load of the container)
–
Truck with the proper dimensions and permissible load
Incoming inspection at arrival
• Visually check for any potential transportation damage(s). If any damages found, mark and record them and
immediately inform your local FIMER representative or your FIMER sales contact.
• Repair any damaged paint. See section Maintenance of painted surfaces.
• Check that the MVCS corresponds to the delivery list and order. Record the deviations (if any) and immediately
inform your local FIMER representative or FIMER sales contact.
Unloading
WARNING!
To prevent damage to the MVCS, keep the delivery packaging and protection canvas on until you install it.
WARNING!
Inspect the MVCS carefully before performing any activity. Check that there is no protuberance or any general poor
condition.
Before unloading, follow these instructions:
1. Protect the corners of the MVCS against shock.
2. Make sure that the terrain is level and sturdy. Consider that the MVCS has an approximate weight of 15 tons.
3. Unload the standard container carrying the MVCS inside. Follow local regulations and applicable standards.
4. Remove all stops, and transportation slings at both ends and laterals.
Tools used for unloading
• Five tons forklift.
• Two guide platforms with length 5 m and width 400 mm.
• Two slings of eight tons. Minimum 5 m.
4 - Storing, lifting and transporting
Содержание MVCS
Страница 1: ...Medium Voltage Compact Skid FIMER solar Hardware manual ...
Страница 2: ......
Страница 49: ...49 ...