15
1
LV Bu Neutral terminal
2
Off-Load Tap changer
3
MV Connectors
4
Earthing terminal and Oil Drain Valve
5
RIS2/DGPT2 (protection device)
6
Oil filling plug
MV Transformer
Technical Datasheet
Minimum Ambient Temperature
-25 °C
Maximum Ambient Temperature (No derating)
60ºC
Max Altitude
<1000 m asl
Reference Standard
IEC60076-1
Cooling type
ONAN
Power @30ºC
Up to 6,66 MVA
Primary voltage
Up to 36 kV
Secondary Voltage
0,8/0,48/0,4 kV
Voltage regulation range
+/- 2x2,5%
Vectorial group
Dyn11
Primary insulation class
24 / 50 / 125 kV
36 / 70 / 170 kV
Secondary insulation class (ph)
3,6/10/40
Secondary insulation class (N)
1,1/10/20
Losses
Standard: EU 548/2014
Optional: EU 2019/1783
1
Short Circuit Impedance
5…8%
Frequency
50/60 Hz
Max Dimensions (LxWxH)
2650x1700x2200
Corrosion class
Standard: C4
Upgrade: C5M
Painting
RAL 7035
Load Power derating
According nº of inverters and environmental conditions
Safety protection device
RIS2/DGPT2 or similar
*This layout may vary depending on final MVCS configuration