20
Type designation label
The figure below shows an example of the type designation label. The label contains the basic data of the unit. It is located inside the AC
cabinet, specifically in auxiliary service board section.
MVCS Configuration
To define a MVCS the following inputs are needed:
Eg:
• String Inverter: PVS-175
• Number of inverters connected to the MVCS: 20
• Medium Voltage Level: 15 kV
With the definition of the inputs above, then a standard MVCS will be configured:
• Skid: C4;
• SWG: 24kV;16kA;CV; 50/51-50N/51N-68 Relay;
• MV Transformer: 15/0,8 Dyn11; 3.700 kVA @30ºC; Losses acording EU 548/2014 Regulation
• AC Cabinet: 20 inputs;10kVA Auxtrafo (0,8/0,4-0,23 kV)
If additional features are needed, then the appropriate optional codes from the following section must be selected:
1
Product description: MVCS + string inverter name
2
General designation: string inverter name + MVCS rated power
3
S/N
4
Manufacturing Year
5
CE marking
Input
Value
String Inverter
Number of inverters connected
Medium Voltage level
3 - Hardware desription