1
SERIES FR702VR
115 and 230 VOLT AC
FUEL TRANSFER PUMP
Owner's Operation & Safety Manual
Models FR702VR & FR702VER
OUTSTANDING FEATURES
•Up to 18 GPM/68 LPM
•UL listed dispenser & motor
•Full 1/3 HP explosion proof motor
•Meter accuracy of ± 1%
GENERAL DESCRIPTION
The FR702VR compact cabinet pump is based on Fill-Rite’s
FR700V positive displacement, direct drive pump, and Fill-Rite’s
series 800C nutating disc flow meter which features a flow rate
of 5 to 20 GPM or 19 to 76 LPM and is accurate to within ±1%.
Depending on product viscosity and nozzle selection, the
FR702VR can deliver up to 18 gallons/68 liters of fluid per
minute. This pumping system is UL listed for use with gasoline
and diesel fuel.
The U.S. gallon meter has three resettable wheels, two unit
wheels and a tenth wheel. It’s non-resettable totalizer has five
unit wheels and a tenth wheel. The optional liter meter has
three unit wheels which can be reset to zero. It’s non-resettable
totalizer has six unit wheels.
OPTIONS
• Automatic nozzles
• Metering in U. S. gallons or liters
• Red or white cabinet paint
• Pedestal for island installations
• 220 VAC, 50/60 Hz
TECHNICAL INFORMATION
D
esign Features:
• 1.25" NPT inlet, 3/4" NPT outlet
• 22 PSI maximum outlet pressure
• Minimum dry vacuum of 10" Hg
• Furnished with 3/4" dia. x 12' hose and manual
nozzle
• Cabinet measures 13"W x 10.94"D x 17.81"H (33 x 27.8 x
43.6 cm)
• Built-in check valve, bypass valve and thermal
expansion valve
• No additional foot valve or check valve needed to
hold prime
• 1/3 HP 115VAC-60Hz, 5.5 amp, 1725 RPM, direct
drive motor
• Ball bearing construction: no lubrication required
• Thermal overload protection
• Explosion proof
• Meter’s mechanical totalizer to 100,000 units
• Meter accuracy is ± 1%
• Unit wheels have large 11/16" (18 mm) figures
• Convenient, large reset knob with positive zero stop
• Not for resale use
• Pre-installed Anti-Siphon Valve
FLUID COMPATIBILITY
If in doubt about compatibility of a specific fluid, contact supplier
of fluid to check for any adverse reactions to the wetted materi-
als in the parts list.
SAFETY INSTRUCTIONS
To ensure safe and efficient operation, it is essential to read
and follow each of these warnings and precautions.
1. Improper use or installation of this product can cause
serious bodily injury or death.
2. Do NOT smoke near pump or use pump near an open flame
when pumping flammable fluids. Fire could result.
3. A Fill-Rite filter should be used on pump outlet to ensure
that no foreign material is transferred to fuel tank.
4. Use gasoline and oil resistant thread sealant or sealant tape
on all threaded joints to protect against leakage.
5. Storage tank should be anchored to prevent tipping in both
the full and empty conditions.
6. To minimize static electricity buildup, only use static wire,
conductive hose when pumping flammable fluids and keep
nozzle in contact with container being filled while filling
container.
7. The pump motor is equipped with thermal overload
protection. If overheated, it will shut off without any damage
to the windings. Be sure to turn off the pump power if this
occurs. When the motor cools, it will restart without warning
if power is on.
8. Take motors needing service to an authorized repair shop to
maintain “explosion proof” and “rain proof” integrity.
9. Do not operate without the check valve (700F2661) in place.
Fluid leakage could result.
DANGER
Electrical wiring should be done by a licensed electrician in com-
pliance with local, state and national electric codes.
NEC/ANSI/NFPA 70, NFPA 30, NFPA 30A, as appropriate to the
intended use of the pump. Threaded rigid conduit, seal fittings
and conductor seal should be used. Pump should be properly
grounded. Improper use or installation of this product can cause
serious bodily injury or death.
WARNING
Do not use this product for fluid transfer into aircraft. This prod-
uct is not suited for use with fluids for human consumption or
fluids containing water.
INSTALLATION
GENERAL
Pumps are furnished with a tank adapter for skid tank mounting;
pedestals are available for island installations. All tanks must be
properly vented. A pressure retaining vent/fill cap can be used to
reduce fuel loss due to evaporation but will reduce flow rate.
Fill-Rite filters are recommended when pumping fuels.
Pump has a built-in check valve with pressure relief to prevent
fluid thermal expansion from causing unsafe system pressures.
Do not use additional check valves or foot valves unless
they have a proper pressure relief valve built into them.
Additional check valves will reduce flow rate.
Use a gasoline and oil resistant pipe sealant on all pipe threads
to protect against leaks.
SKID TANK MOUNTING
1. Cut a 1 1/4" pipe that will extend to at least 3"
(8 cm) above bottom of tank when screwed into tank
adapter and tank adapter is screwed into tank flange.
2. Screw pipe into tank adapter, then screw tank adapter into
tank flange.
3. Mount pump on tank adapter.