Modbus TCP
The SBPC-21-EN conforms to Modicon Open Modbus/TCP Specification, Release 1.0 (March 29,
1999). The SBPC-21-EN provides complete Class 0 conformance, complete Class 1 conformance,
and partial Class 2 conformance. The SBPC-21-EN can handle 8 simultaneous connections.
The following table lists the Modbus functions supported by the SBPC-21-EN:
Table 1-4
CODE
FUNCTION NAME
CLASS
AFFECTS AREA
ADDRESSING
METHOD
01 Read
Coils
1 IN/OUT
Bit
02 Read
Input
Discretes
1 IN/OUT
Bit
03
Read Multiple Registers
0
IN/OUT
Word
04 Read
Input
Registers
1 IN/OUT
Word
05 Write
Coil
1 OUT
Bit
06
Write Single Register
1
OUT
Word
07 Read
Exception
Status
1 -
-
15
Force Multiple Coils
2
OUT
Bit
16
Force Multiple Registers
0
OUT
Word
22
Mask Write Register
2
OUT
Word
23 Read/Write
Registers
2 IN/OUT
Word
The following table lists the Modbus/TCP error codes:
Table 1-5
EXCEPTION
CODE
NAME
DESCRIPTION
01
Illegal Function
The SBPC-21-EN does not support the function code in the query.
02
Illegal Data Address
The data address received in the query is outside the initialized memory area.
03
Illegal Data Value
The data in the request is invalid.
07-02-2004
Figure Sheet 1-849-C
Page 11
Содержание SBPC-21-EN
Страница 2: ...07 02 2004 Figure Sheet 1 849 C...
Страница 4: ...07 02 2004 Figure Sheet 1 849 C Page ii...
Страница 18: ...07 02 2004 Figure Sheet 1 849 C Page 12...
Страница 22: ...07 02 2004 Figure Sheet 1 849 C Page 16...
Страница 38: ...07 02 2004 Figure Sheet 1 849 C Page 32...
Страница 42: ...07 02 2004 Figure Sheet 1 849 C Page 36...