SBPC-21-EN Error Codes
The 7-segment LED digit on the SBPC-21-EN main board is used to indicate errors or other potential
problems. See page 2 of this manual for the location of this LED. The error codes are divided into the
categories listed below. Since there is only a single-digit display and the error codes are 3 digits in
length, the error codes are displayed in three parts. The most significant digit will appear first followed
by the second and third digits. The display will go blank for a moment and the cycle repeats unless the
SBPC-21-EN has been configured to attempt to restart after an error. If this is the case, the error will
only cycle once. All state machine errors 5XX are considered nonfatal and only cycle once. Below are
the error codes and their meanings.
Table 1-2
SBPC PROCESSOR ERRORS
F01
Processor attempted to execute and undefined instruction.
F02
Software interrupt vector occurred.
F03
Attempt to fetch instruction from invalid memory.
F04
Attempt to read data from invalid memory.
F05
Reserved exception vector.
F06
FLASH memory checksum fault.
F07
Pool memory allocation error.
F08
Byte memory allocation error.
F09
Unable to create thread.
F0A
Unable to create event.
F0B
Unable to create semaphore.
F0C
Unable to create mutex.
F0D
Unable to create queue.
F0E
Unable to write to queue.
F0F
Console I/O error.
Errors that begin with ‘F’
are unrecoverable faults.
The SBPC cannot
participate in FifeNet or
Ethernet operations. In
the default configuration,
the SBPC will attempt to
restart.
COMMUNICATION MODULE ERRORS
E01
The configuration matrix is corrupted.
E02
No HMS Anybus module detected.
E03
Anybus module failed to initialize (no interrupt received).
E04
Anybus module failed to initialize (interrupt stuck).
E05
Anybus module failed to initialize (mailbox not ready).
E06
Anybus mailbox timeout.
E07
Anybus mailbox response indicated error.
E08
Anybus mailbox response timeout.
E09
Anybus dual-port RAM fault.
E0A
Anybus output area release timeout.
E0B
Anybus initialization timeout.
Errors that begin with ‘E’
are associated with the
Ethernet interface. In
the default configuration,
the SBPC will attempt to
restart. With the
exception of error ‘E01,’
FifeNet is functional;
however, the default
configuration will attempt
to restart which will
interrupt FifeNet.
STATE MACHINE ERRORS
501
State machine file is corrupted.
502
State machine is disabled.
503
State machine started in shutdown mode.
504
Bad state machine instruction encountered.
505
State machine instruction fetch from address is out of range.
506
State machine stack error (too many nested calls).
507
State machine stack error (too many returns).
508
State machine attempted divide by zero.
509
State machine tried to access more than four timers.
50A
State machine variable address is out of range.
Errors that begin with ‘5’
are related to the state
machine capability of the
SBPC. These errors are
cycled only once and do
not cause the SBPC to
restart.
07-02-2004
Figure Sheet 1-849-C
Page 5
Содержание SBPC-21-EN
Страница 2: ...07 02 2004 Figure Sheet 1 849 C...
Страница 4: ...07 02 2004 Figure Sheet 1 849 C Page ii...
Страница 18: ...07 02 2004 Figure Sheet 1 849 C Page 12...
Страница 22: ...07 02 2004 Figure Sheet 1 849 C Page 16...
Страница 38: ...07 02 2004 Figure Sheet 1 849 C Page 32...
Страница 42: ...07 02 2004 Figure Sheet 1 849 C Page 36...