Specifications
Power:
24VAC ± 10%, 50-60Hz, 20VA power consumption
(Single Class II 70VA or 100VA option available)
Physical:
Rugged plastic housing protects circuitry.
Environmental
Operating Range
: 40° to 130°F (-17.8° to 54.4°C); 10 to 90% relative humidity, non-condensing
Digital Outputs:
Five digital outputs relay contacts rated at 1A resistive @ 24VAC; configured as dry contact,
normally open.
Universal Inputs:
8 inputs. Inputs 1 and 2 are configurable for 0-5VDC, 10K ohm thermistor,
or dry contact; inputs 3 and 4 support thermistor or dry contact only; inputs 5 and 6 support
thermistor, dry contact, or LogiStat. Inputs 7 and 8 are used for 1-10K adjustment pots or dry
contacts.
Standard
Comm Port:
3-pin port configurable for ARC156 (BACnet-over- ARC156) or
Communication
EIA-485communications (BACnet MS/TP, Modbus RTU, orN2).
Ports: Rnet Port:
4-pin port for interface with remote mounted BACview6 or RS sensors
Local Access Port:
For local communication with a laptop computer running WebCTRL or
for communication with a BACview6.
Status Indication:
Visual (LED) status of network communication, running, errors, power, and
all digital outputs
Battery:
Lithium 3V coin cell battery, CR2032, provides a minimum of 10,000 hours of
Data retention during power outages
Protection:
Surge and transient protection circuitry for power and communications.
Listed by:
FCC Part 15 - Subpart B - Class A. Pending listings at the time of publishing
this document: UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), CE (1997).
Weight:
0.6 lbs. (0.27 Kg).
Overall
Dimensions:
5-1/16” (width) by 5-11/16” (height) by 1-1/2” (recommended panel depth).
129mm (width) by 144mm (height) by 38mm (recommended panel depth).
Mounting Hole
Dimensions:
Two mounting holes center line as at left with 5-9/16” (141mm)
Spacing (height)
5
Содержание AHP 641-224
Страница 1: ...1 I O ZONE 560 583 641 224 641 242 641 237 USERS GUIDE...
Страница 21: ...Figure 12 Typical water to air applications Water to Air Standard 21...
Страница 22: ...Figure 13 Typical water to air applications Water to Air with Hot Gas Re Heat 22...
Страница 23: ...Figure 14 Typical water to air applications Water to Air with CO2 and OA Damper 23...
Страница 24: ...Figure 15 Typical water to air application Discharge Air Control with Modulating Reheat Valves 24...
Страница 25: ...25...
Страница 26: ...Figure 16 Typical water to air integration points list 26...
Страница 33: ...Figure 17 Typical water to water applications Water to Water Standard 33...
Страница 34: ...34...
Страница 35: ...Figure 18 Typical water to water integration points list 35...
Страница 36: ...BACview Termination Detail 36...
Страница 40: ...40 NOTES...
Страница 41: ...41 NOTES...