Single Outside Air Temperature (OAT) Reset:
OAT> OAT Reset °F (adj.):
Controller will initiate cooling call to run compressors and modulate Re-heat Valve only when
the outside air temperature is greater than 55°F (Factory Default)
OAT< OAT Reset °F (adj.):
Controller will initiate a call for heating. Straight cool units will run their fan continuously or if the
unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to maintain its
static pressure setpoint.
Multiple Outside Air Temperature (OAT) Reset:
OAT Reset °F < OAT< OAT Reset 2 °F (adj.):
Controller will command the unit to run free-cooling operation the fan will run continuously or if
the unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to maintain
its static pressure setpoint.
OAT Reset 2 °F < OAT< OAT Reset 3 °F (adj.):
Controller will command the unit to run single stage of cooling operation, the valve will be set for
cooling operation and the first compressor will be commanded on, the fan will run continuously
or if the unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to
maintain its static pressure setpoint and the re-heat valve will be modulated to maintain a 65°F
(Factory Default (adj.)) discharge air temperature setpoint .
OAT > OAT Reset 3 °F (adj.):
19
Содержание AHP 641-224
Страница 1: ...1 I O ZONE 560 583 641 224 641 242 641 237 USERS GUIDE...
Страница 21: ...Figure 12 Typical water to air applications Water to Air Standard 21...
Страница 22: ...Figure 13 Typical water to air applications Water to Air with Hot Gas Re Heat 22...
Страница 23: ...Figure 14 Typical water to air applications Water to Air with CO2 and OA Damper 23...
Страница 24: ...Figure 15 Typical water to air application Discharge Air Control with Modulating Reheat Valves 24...
Страница 25: ...25...
Страница 26: ...Figure 16 Typical water to air integration points list 26...
Страница 33: ...Figure 17 Typical water to water applications Water to Water Standard 33...
Страница 34: ...34...
Страница 35: ...Figure 18 Typical water to water integration points list 35...
Страница 36: ...BACview Termination Detail 36...
Страница 40: ...40 NOTES...
Страница 41: ...41 NOTES...