Water to Air Operation
General Description
The Heat Pump Factory mounted I/O Zone 560 or 583 DDC Controllers are factory configured
with the Water to Air application program and factory installed in the unit to be job site
configureable to run.
The unit will operate in a 100% stand-alone control mode or connect to a Building Automation
System (BAS) using open protocols BACnet® (ARCNET and MS/TP), Modbus RTU, N2 or
LonWorks® (additional network interface board required for LonWorks® option).
The point mapping to all of these protocols is available in
www.fhp-mfg.com
and can be pre-set,
so that the protocol and baud rates desired can be easily field-selected and commissioned
without the need for any additional downloads or technical assistance.
The DDC Controller also supports communications to intelligent RS Room sensors and
BACview keypad/display panels.
Key Features and Benefits
I/O point count: 5 Digital outputs and 6 Universal inputs
Powerful high speed microprocessor with 1MB Flash memory and 1MB of battery-backed
RAM
Built-in protocol support: BACnet® (ARCNET and MS/TP), Modbus, N2 and LonWorks®
(additional network interface board required for LonWorks® option)
Built-in local access support: BACview6 keyboard/display and Intelligent RS Room
sensors
On-board lithium battery holds Controller time clock settings
Program archived in non-volatile memory allows unit to be ready after long periods of
power outages.
10
Содержание AHP 641-224
Страница 1: ...1 I O ZONE 560 583 641 224 641 242 641 237 USERS GUIDE...
Страница 21: ...Figure 12 Typical water to air applications Water to Air Standard 21...
Страница 22: ...Figure 13 Typical water to air applications Water to Air with Hot Gas Re Heat 22...
Страница 23: ...Figure 14 Typical water to air applications Water to Air with CO2 and OA Damper 23...
Страница 24: ...Figure 15 Typical water to air application Discharge Air Control with Modulating Reheat Valves 24...
Страница 25: ...25...
Страница 26: ...Figure 16 Typical water to air integration points list 26...
Страница 33: ...Figure 17 Typical water to water applications Water to Water Standard 33...
Страница 34: ...34...
Страница 35: ...Figure 18 Typical water to water integration points list 35...
Страница 36: ...BACview Termination Detail 36...
Страница 40: ...40 NOTES...
Страница 41: ...41 NOTES...