29
Sequence of Operation
Run Conditions:
The unit will run according to a user definable time schedule, dry contact (physical digital input
number 1), manual ON command from BACview control interface or via third party front end
start command (BV software point). When commanded to run the unit will operate in the
following modes:
Occupied Mode
: The unit will maintain
A 54°F (12°C) adj. Cooling setpoint
A 105°F (40 °C) adj. Heating setpoint
Unoccupied Mode (night setback):
The unit will maintain
A 74°F (12°C) adj. Cooling setpoint.
A 85°F (30°C) adj. Heating setpoint.
The values above can be changed by the commissioning agent by using the BACview or via the
BAS.
Auto Changeover Mode
When operating on Changeover mode the unit will automatically change from heat to cool and
vice versa, by using the
Changeover Setpoint
and the
Changeover Deadband
.
These points can be changed by the commissioning agent, the factory defaults are 65°F and
3°F (18°C and 2°C) respectively, the units will enter in cooling or heating mode according to the
following:
Содержание AHP 641-224
Страница 1: ...1 I O ZONE 560 583 641 224 641 242 641 237 USERS GUIDE...
Страница 21: ...Figure 12 Typical water to air applications Water to Air Standard 21...
Страница 22: ...Figure 13 Typical water to air applications Water to Air with Hot Gas Re Heat 22...
Страница 23: ...Figure 14 Typical water to air applications Water to Air with CO2 and OA Damper 23...
Страница 24: ...Figure 15 Typical water to air application Discharge Air Control with Modulating Reheat Valves 24...
Страница 25: ...25...
Страница 26: ...Figure 16 Typical water to air integration points list 26...
Страница 33: ...Figure 17 Typical water to water applications Water to Water Standard 33...
Страница 34: ...34...
Страница 35: ...Figure 18 Typical water to water integration points list 35...
Страница 36: ...BACview Termination Detail 36...
Страница 40: ...40 NOTES...
Страница 41: ...41 NOTES...