The controller will only allow supplemental heating if the unit is configured to allow this
operation, units equipped with hot gas re heat valves or damper control enable will not have
supplemental electric heat functionality.
Discharge Air Temperature:
The controller will monitor the discharge air temperature to be located at discharge side of coil. If
the supplemental heating is installed then sensor will be in the discharge side of heating coil.
Alarms will be provided as follows:
High Discharge Air Temp:
If unit running in cool mode and the discharge air temperature is
greater than 70°F (adj.).
Low Discharge Air Temp:
If unit running in heat mode and the discharge air temperature is
less than 75°F (adj.).
Discharge Air Sensor Failure:
If discharge air sensor outside of normal operating limits.
Discharge Air Control
On units with factory mounted modulating re-heat valves the controller will operate the unit to
maintain a particular discharge temperature setpoint. The discharge air temperature sensor
(DATS) will be located at discharge side of coil preferable 3/4 downstream of the total length of
the duct work.
The controller can operate on single or Multiple Outside Air Temperature Reset, the controller
will monitor the value of the Outside Air temperature via a BACnet point or via a physical point
terminated in one of the controllers available inputs. The controller will stage the unit’s
compressors and modulate the re-heat valve mode to maintain the Discharge Air Setpoint (User
adjustable).
Two modes are selectable for Discharge Air Control (DAC) Applications are as follows:
Single Outside Air Temperature Reset point
Multiple Outside Air Temperature Reset points
18
Содержание AHP 641-224
Страница 1: ...1 I O ZONE 560 583 641 224 641 242 641 237 USERS GUIDE...
Страница 21: ...Figure 12 Typical water to air applications Water to Air Standard 21...
Страница 22: ...Figure 13 Typical water to air applications Water to Air with Hot Gas Re Heat 22...
Страница 23: ...Figure 14 Typical water to air applications Water to Air with CO2 and OA Damper 23...
Страница 24: ...Figure 15 Typical water to air application Discharge Air Control with Modulating Reheat Valves 24...
Страница 25: ...25...
Страница 26: ...Figure 16 Typical water to air integration points list 26...
Страница 33: ...Figure 17 Typical water to water applications Water to Water Standard 33...
Страница 34: ...34...
Страница 35: ...Figure 18 Typical water to water integration points list 35...
Страница 36: ...BACview Termination Detail 36...
Страница 40: ...40 NOTES...
Страница 41: ...41 NOTES...