6
Commissioning
38
Festo – SBRD-EN – 2017-11 – English
Note
Protocol-based I/Os can only be requested if they were previously stored in the CCS
software CCS in the selected job with the corresponding name.
An error message appears if no protocol-based I/Os were created.
Details on configuration of protocol-based I/Os are located in the online help of the CCS
software.
The values are output only if the name of the protocol-based I/O was written completely
and correctly.
Use
none
of the following characters for names of the protocol-based I/Os when
configuring the job in the CSS:
–
Square brackets [ ]
–
Quotation marks “ ”
–
Umlauts
–
Special characters
Pay attention to capital and small letters.
If the protocol-based I/Os exist and use the Telnet protocol, the result depends on the output format:
–
Telnet – Part Detector: binary coded
–
Telnet – Data Collection: binary coded
–
Telnet – XML: XML coded
Note
The structure and contents of the protocol-based I/Os are displayed in CCS
in the results window of the respective I/O. As a result, programming of the controller
for acceptance of the data can be implemented easily
IMAGE
Image evaluation
This IMAGE command is allowed only in the evaluation mode triggered and free wheel unit. The com
mand performs a complete evaluation. The inspection results and characteristics are entered at
the corresponding flag word addresses.
CHANGEPRG
CHANGEPRG job number
The job can be changed with this command. The values 1 to 255 are allowed as job number.
Requirements:
–
The device is not in the configuration mode. If the device is in the configuration mode, only the new
job number is stored without changing into the job. If the configuration mode is ended, the device
changes into the job with this job number.
–
The device is ready for operation:
ready for operation output signals operational readiness.