3. Input module CPX-P-8DE-N-...
3-52
Festo P.BE-CPX-P-EA-EN en 1209NH English
Module error LED
LED (red)
Process
Status
Significance / error handling
LED not illu-
minated
ON
OFF
Trouble-free operation
None
LED flashes
error-
specific
Minor error
(e.g. parameterisation er-
ror)
Check the parameterisation measures
conducted and, if necessary, conduct
the parameterisation process again
with the correct parameters
1)
LED
illuminated
ON
OFF
Serious error
(e.g module/channel
failed)
Check the supply voltage; power
Off/On necessary; repeat occurrence
means servicing required
1)
Details
section 3.3.9.
Tab. 3/41:
Module error LED
Channel error LED
LED (red)
Process
Status
Significance / error handling
LED not illu-
minated
ON
OFF
Trouble-free operation
None
LED flashes
error-
specific
Wire break
Eliminate wire break
LED
illuminated
ON
OFF
Error on the corresponding
channel (e.g. short circuit
or limit value reached)
Eliminate error on the corresponding
channel; check connected field device
if necessary
Tab. 3/42:
Channel error LED
Содержание CPX-P-8DE-N Series
Страница 2: ......
Страница 34: ...1 Overview and connection technology 1 14 Festo P BE CPX P EA EN en 1209NH English...
Страница 35: ...Mounting and dismantling 2 1 Festo P BE CPX P EA EN en 1209NH English Chapter 2 Mounting and dismantling...
Страница 50: ...2 Mounting and dismantling 2 16 Festo P BE CPX P EA EN en 1209NH English...
Страница 51: ...Input module CPX P 8DE N 3 1 Festo P BE CPX P EA EN en 1209NH English Chapter 3 Input module CPX P 8DE N...
Страница 113: ...Technical appendix A 1 Festo P BE CPX P EA EN en 1209NH English Appendix A Technical appendix...
Страница 125: ...Index B 1 Festo P BE CPX P EA EN en 1209NH English Appendix B Index...
Страница 126: ...B Index B 2 Festo P BE CPX P EA EN en 1209NH English Table of contents B Index B 1...
Страница 132: ...B Index B 8 Festo P BE CPX P EA EN en 1209NH English...