3. Input module CPX-P-8DE-N-...
3-10
Festo P.BE-CPX-P-EA-EN en 1209NH English
Connection of non-actuated mechanical contacts
When connecting non-actuated mechanical contacts no wire
break or short-circuit monitoring function is possible. When
using an active wire break and short-circuit monitoring func-
tion an open contact is identified as a wire break and a closed
contact is identified as a short circuit.
If you are using non-actuated mechanical contacts:
•
Disable the wire break and short-circuit monitoring
function for the respective channels (
Tab. 3/22 and
Tab. 3/23).
1
Non-actuated
mechanical
contact
1
Fig. 3/4:
Connection of non-actuated mechanical contacts