3. Input module CPX-P-8DE-N-...
3-23
Festo P.BE-CPX-P-EA-EN en 1209NH English
3.3.6
Operating mode C, D - frequency measurement
In the frequency measurement procedure rising edges of the
digitised signal are counted within a parameterised gate time
and the frequency subsequently calculated (f = n/t). If the
value exceeds or falls below the specified limit values, the bit
assigned to the relevant channel is set in byte 0 of the PII
(
Tab. 3/9).
Certain parameter alterations cause an initialisation of the
respective channel. This stops the current frequency meas-
urement (
section 3.3.8).
Channel
Frequency measurement
0 … 3
Control possibilities
– Start and stop via byte 0 of the PIO
– Current frequency in byte 2 … 9 of the PII
1)
– Alarm signal in byte 0 of the PII
Parameterisable properties:
– Gate time
– Lower and upper limit value
– Input debounce times
2)
(signal extension times are ignored)
– Diagnostic response upon reaching limit values
Maximum values of operating mode C:
– max. signal frequency (f
max
): 1250 Hz
– min. pulse length: 400 µs
– min. signal pause: 400 µs
– Range of values for lower limit value: 0 … 999
– Range of values for upper limit value: 1 … 1000
Maximum values of operating mode D – channel 0 only:
– max. signal frequency (f
max
): 12500 Hz
– min. pulse length: 40 µs
– min. signal pause: 40 µs
– Range of values for lower limit value: 0 … 9999
– Range of values for upper limit value: 1 … 10000
1)
Only applicable for extended process image (
Tab. 3/10)
2)
Only effective in operating mode C: The edges of the debounced
signal are counted. The debounce time limits the max. measur-
able frequency. At a debounce time of 3 ms, for example, this is
approx. 166 Hz.
Tab. 3/15:
Frequency measurement (operating mode C
and D)
Содержание CPX-P-8DE-N Series
Страница 2: ......
Страница 34: ...1 Overview and connection technology 1 14 Festo P BE CPX P EA EN en 1209NH English...
Страница 35: ...Mounting and dismantling 2 1 Festo P BE CPX P EA EN en 1209NH English Chapter 2 Mounting and dismantling...
Страница 50: ...2 Mounting and dismantling 2 16 Festo P BE CPX P EA EN en 1209NH English...
Страница 51: ...Input module CPX P 8DE N 3 1 Festo P BE CPX P EA EN en 1209NH English Chapter 3 Input module CPX P 8DE N...
Страница 113: ...Technical appendix A 1 Festo P BE CPX P EA EN en 1209NH English Appendix A Technical appendix...
Страница 125: ...Index B 1 Festo P BE CPX P EA EN en 1209NH English Appendix B Index...
Страница 126: ...B Index B 2 Festo P BE CPX P EA EN en 1209NH English Table of contents B Index B 1...
Страница 132: ...B Index B 8 Festo P BE CPX P EA EN en 1209NH English...