3
Mounting and installation
20
Festo – P.BE-CPX-FB37-EN – 1406NH – English
3.2.9
Setting the EtherCAT address
You can assign a free EtherCAT address (Explicit Device ID) to the bus node by using DIL switch 3.
Setting an EtherCAT address is optional (e.g. for the Hot-Connect function).
You can set the EtherCAT address in binary coded format by using switch elements 1 to 8.
If the EtherCAT address 0 is set, the programmed address in the EEPROM is used (factory
setting).
1 to 255 are thereby available as possible EtherCAT addresses.
Example: Set EtherCAT address 77
DIL switch 3
1
2
3
4
5
6
7
8
DIL switch element
1
2
3
4
5
6
7
8
Switch position
ON
Off
ON
ON
Off
Off
ON
Off
Binary
1
0
1
1
0
0
1
0
Potency (significance)
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
Numerical value (decim-
al)
1
0
4
8
0
0
64
0
EtherCAT address
1 + 0 + 4 + 8 + 0 + 0 + 64 + 0 =
77
Tab. 3.6
Setting the EtherCAT address with DIL switch 3
The set EtherCAT address (Explicit Device ID) must be activated.
To do this in the TwinCAT 3.x configuration tool, select the following:
EtherCAT
Advanced settings
General
Identification
Explicit Device Identi-
fication (ADO 0x0134) (
Fig. 3.3).
Fig. 3.3
Selecting “Explicit Device Identification (ADO 0x0134)” (TwinCAT 3.x)