3
Mounting and installation
Festo – P.BE-CPX-FB37-EN – 1406NH – English
17
3.2.4
Setting the operating mode
You can set the operating mode of the bus node with switch element 1.1 of DIL switch 1.
Operating mode
Setting DIL switch 1
Remote I/O
DIL 1.1:
OFF
(factory setting)
All functions of the CPX terminal are controlled directly by
the EtherCAT controller or a higher-level PLC.
The bus node thereby takes over the connection to the
EtherCAT network.
Remote controller
DIL 1.1:
ON
A CPX-FEC or CPX-CEC integrated into the terminal
controls all functions.
The bus node thereby takes over the connection to the
EtherCAT network.
Tab. 3.1
Setting the operating mode
3.2.5
Configuring the EtherCAT addressing type
Use switch element DIL 1.2 of DIL switch 1 to switch between Modular Device Profile and fixed I/O size
(
Section 4.5.1).
EtherCAT addressing type
Setting DIL switch 1
Modular Device Profile (MDP) active
DIL 1.2:
OFF
(factory setting)
Fixed I/O size active (64 byte I/O)
(compatible with the bus node CPX-FB38
)
DIL 1.2:
ON
Tab. 3.2
Configuring the EtherCAT addressing type