3
Mounting and installation
16
Festo – P.BE-CPX-FB37-EN – 1406NH – English
3.2.2
Arrangement of the DIL switches
There are 3 DIL switches available for configuring the bus node. They are located underneath the DIL
switch cover.
1
2
3
1
DIL switch 1: Bus node operating mode
2
DIL switch 2: Diagnostics mode, number of
I/O bytes, bootloader
3
DIL switch 3: EtherCAT address of the bus
node
Fig. 3.2
DIL switches on the bus node
3.2.3
Setting the DIL switches
1. Switch off the power supply.
2. Remove the cover (
Section 3.2.1).
3. Perform the required settings (
Tab. 3.1 … Tab. 3.6).
4. Replace the cover (
Section 3.2.1).
Changes to the DIL switches only take effect when the bus node is restarted.