Festo — CPX-F8DE-P — 2022-10d
Commissioning
63
Overview of module parameters CPX-F8DE-P
Function number
1)
Bit
Module parameters
Default
4828 + m * 64 +22
0 ... 7
Position of the 10x DIL switch
for the PROFIsafe address of the
module, bits 0... 7
0
1)
4828 + m * 64 +23
0, 1
Position of the 10x DIL switch
for the PROFIsafe address of the
module, bits 8 and 9
0
1)
1) Parameters read-only via operator unit and command interpreter (CI).
Tab. 28: Overview – module parameters CPX-F8DE-P
Module parameter: DIL switch setting
Operator unit
Func-
tion no.
4828 + m * 64 +22
m = module number (0 … 47)
4828 + m * 64 + 23
Descrip
tion
Indicates the switch setting of the PROFIsafe address selector switch on the input module.
In addition to the PROFISsafe parameter F_Dest_Add (
4.6 Setting the PROFIsafe param-
eters) the setting of the address selector switch can be read out via CPX parameters for
diagnostic purposes – e.g. with the operator unit (read only).
Bit
low byte (4828 + m * 64 + 22)
[PROFIsafe Addr]
Bit 0:
SW 0
Bit 1:
SW 1
...
Bit 7:
SW 7
high byte 4828 + m * 64 + 23)
Bit 0:
SW 8
Bit 1:
SW 9
Bit 2 ... 7: reserved or 0
Values
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
SW 7 SW 6 SW 5 SW 4 SW 3 SW 2 SW 1 SW 0 low byte
0
0
0
0
0
0
SW 9 SW 8 high byte
0: switch element is set to OFF
1: switch element is set to ON
[0]
[1]
Com-
ment
This parameter can only be changed by changing the DIL switch setting (read only).
Tab. 29: DIL switch setting