Festo — CPX-F8DE-P — 2022-10d
Commissioning
Module (order code)
Module identification
1)
Assigned I/O bytes
2)
CPX-F8DE-P
F8DI-P
6 bytes I + 7 bytes O
1) Module identifier in operator unit
2) 4 bytes each are used exclusively for PROFIsafe communications
Tab. 26: Module identifier of the input module CPX-F8DE-P
4.4
Preparing for commissioning
1. Ensure that the CPX terminal is mounted correctly
è
CPX system description.
2. Check the wiring (connecting cables, contact assignment)
3.2.1 Pin allocation on the manifold block CPC-M-AB-4-M12X2-5POL-T.
3. Dismantle the manifold block of the input module
3.3.1 Demounting the electronics module.
4. Check that the input module is in good condition.
5. Set the PROFIsafe address with DIL switches on the input module and install the manifold block
3.3.2 Installing the electronics module.
4.5
Commissioning steps
Detailed information about configuring, programming and commissioning in combination with the
relevant F-Host can be found in the F-Host manufacturer’s documentation.
Information on the configuration and commissioning of the CPX terminal can be found in the descrip-
tion of the bus node.
1. Integrate the GSDML/GSD file in the configuration software of the F-Host
è
Description of the bus node.
2. Configure and parameterise the CPX terminal including the input module with the configuration
software of the F-Host.
–
Add the CPX terminal to the configuration
è
Description of the bus node.
–
If necessary: set the starting addresses for inputs and outputs.
–
Set default parameters on the input module.
–
Set PROFIsafe parameters of the input module
4.6 Setting the PROFIsafe parameters.
3. Create and load the safety program.
4. Commission the CPX terminal on the fieldbus (PROFIBUS or PROFINET IO) and validate the
behaviour in the test run.
4.6
Setting the PROFIsafe parameters
PROFIsafe-specific parameters can be viewed or set with the F-Host configuration device (e.g. HW
Config). They are marked in accordance with the PROFIsafe profile in the GSDML/GSD file. They can
only be accessed by entering the password in the F-Host.
The function mode is set via the output data on the process image
2.2.3 Bit pattern of the output and input data (F-user data).