Festo — CPX-F8DE-P — 2022-10d
Technical data
87
Electrical characteristic values
Max. output current at 24 V terminals
[A]
2
Max. total current per input module
[A]
3
Cable lengths to sensor
Cable type LiFY11Y-OB, unshielded,
3 x 0.14 mm
2
[m]
200
Cable type LiF9Y11Y, unshielded,
4 x 0.10 mm
2
[m]
200
Cable type LiYCY, shielded, 4 x 0.14 mm
2
[m]
200
Tab. 43: Electrical characteristic values
Properties of the clock signals
Duty cycle
[ms]
50 (
_
6)
Pulse duration
[ms]
12
Max. time delay for input signal after clock signal
with falling edge
[ms]
1.7
with rising edge
(switching the sensor on again)
[ms]
25
Tab. 44: Properties of the clock signals
Module characteristic values
Function mode
0
1
2
3
4
5
6
7
8
9
10
Module code
28d (1Ch)
Sub-module code
1d (01h)
No. of inputs
8
Switching logic at inputs
PNP (positive switching)
Compatible with fast start-
up (FSU)
Yes
Time for switch-on phase
until input module is ready
(start-up)
[s]
<
2
Max. tolerance time until
diagnostic message of
channel fault
[s]
-
-
-
0.5
10
0.5
0.5
10
2
2
2
Tab. 45: Module characteristic values