4
Commissioning
Festo – P.BE-CPX-CTEL-EN – 1601b – English
31
4.5
Notes on operation
Warning
Unintentional movement of the connected actuators as a result of accidentally inter
changing the connected I-Port devices.
Caution with subsequent modification of the I-Port assignment:
Make sure that devices are not separated from an I-Port and accidentally connected
to another I-Port. Use the inscription labels (type IBS-6x10 or IBS-9x20) in order
to uniquely identify the devices.
Before starting the system, check whether the I-Port assignment corresponds to
the configuration in the host system.
Warning
Accidental activation of actuators!
An incorrect status of the valves and outputs can lead to dangerous situations!
Make sure that valves and outputs are put in a safe status when malfunctions occur.
Note
Please note the following if the outputs of a valve terminal are reset after a master stop,
fieldbus interruption or malfunction:
–
Monostable valves move to the initial position
–
Double-solenoid valves remain in the current position
–
Mid-position valves go into mid-position (pressurized, exhausted or closed, depending on
valve type).
Observe the product specific instructions in the documentation supplied with the
valve terminal components.