5
Diagnostics and error handling
Festo – P.BE-CPX-CTEL-EN – 1601b – English
43
5.2.2
Diagnostic/error messages by CPX error numbers
Tab. 5.3 shows an overview of the CPX errors as well as possible causes and information for error hand
ling.
CPX error
number
Description of possible causes
Error handling
0
Device OK
No action required
1
General error
–
Device NOK, general diagnostics
–
Hardware error – device replacement
–
Component error – repair or
replacement
–
General error in the power supply
–
Fuse triggered
–
Device software error
Check device, eliminate errors
–
Mass error
–
Temperature overload
Check the installation
–
Technology-specific application error
Reset device
Measuring range exceeded
Check application
2
Short circuit
Check the installation
3
Wire break
Check the installation
5
Error in the power supply
–
Primary voltage/main power supply
too low
–
Undervoltage PL Device supply
(only relevant if PL monitoring
is active in a device)
Check power supply
9
Below minimum value
–
Device temperature limit fallen below
Check the installation
–
Error in memory buffering
–
Low battery level
Check batteries
10
Maximum value not reached
–
Device temperature limit exceeded
Check the installation
–
Primary voltage/main power supply
too low
Check power supply
17
Incorrect I/O length
CPX system start with setting “Stored
parameters”
Use system setting “Standard
parameter” at the start of the CPX
terminal
24
Process variable range underflow
Process data inconsistent, check
25
Process variable range overflow
Process data inconsistent, check
Содержание CPX-CTEL-4-M12-5POL
Страница 58: ......