A
Commissioning
Festo – P.BE-CPX-CTEL-EN – 1601b – English
51
Power supply
Operation/load voltage range
[V DC]
18 … 30
Recommended minimum voltage for load
voltage supply U
VAL
(PL) with operation of
devices on I-Port connecting cables
,
5 m
[V DC]
21.6 (24 – 10 %)
Nominal operating voltage
[V DC]
24
Intrinsic current consumption at 24 V from
operating voltage supply U
EL/SEN
(without connected devices)
[mA]
typ. 65
Maximum current consumption per I-Port at 24 V
from operating voltage supply U
EL/SEN
(PS)
[A]
1.6
from load voltage supply U
VAL
(PL)
[A]
1.6
Electrical isolation
between operating voltage supply U
EL/SEN
and load voltage supply U
VAL
Yes, with potential-isolated supply
Supply PS/PL between the I-Ports
No
Functional earth connection
Optional, through earthing plate
Mains buffering time
[ms]
10