IO-Link
event
code hex
Diagnostics ID
hex
Message
Description
1806h
1807h
01
|
01
|
010B
Short circuit/overload
in sensor supply
Diagnost-
ic status
Error
Temperature
–
overload
Remedy
–
4000h
03
|
01
|
0142
Temperature error;
overload
Diagnost-
ic status
Error
Device overtemperature
Remedy
–
Temperature display plaus-
ible?
–
Device fan defective?
–
Device overloaded?
–
Check installation conditions,
is filter of control cabinet fan
clogged?
–
Check drive layout (possible
overloading during continu-
ous operation)
4210h
03
|
01
|
002F
Device overtemperat-
ure
Diagnost-
ic status
Error
Device undertemperature
Remedy
–
Check ambient conditions.
4220h
03
|
01
|
002D
Device undertemper-
ature
Diagnost-
ic status
Error
Hardware error of the IO-Link device
Remedy
–
Repair or replace IO-Link
device.
5000h
10
|
02
|
0145
Device hardware error
Diagnost-
ic status
Error
Malfunction of a component of the IO-Link
device
Remedy
–
Repair or replace IO-Link
device.
5010h
10
|
02
|
0146
Malfunction of a
device component
Diagnost-
ic status
Error
Diagnostics and fault clearance
22
Festo — CPX-AP-I-4IOL-M12 — 2020-03