8.1
Address space (data length inputs/outputs)
The address space (data length inputs/outputs) provided by the module can be set using software.
The following variants for setting the address space (data length inputs/outputs) are possible:
Module [byte]
per port [byte]
Variant
Module code
(hex/dec)
Supported
network
1)
Inputs
2)
Outputs
Inputs
Outputs
2
0x200E/8206
PB, EP, EC
2_OE
0x200F/8207
PN, EP
12
8
2
2
4
0x2010/8208
PB, EP, EC
4_OE
0x2011/8209
PN, EP
20
16
4
4
8
3)
0x2009/8201
PB, EP, EC
8_OE
0x200D/8205
PN, EP
36
32
8
8
16
0x2012/8210
PB, EP, EC
16_OE
0x2013/8211
PN, EP
68
64
16
16
32
0x2014/8212
PB, EP, EC
32_OE
0x2015/8213
PN, EP
132
128
32
32
1) PB = PROFIBUS; PN = PROFINET; EP = EtherNet / IP; EC = EtherCAT
2) The last 4 input bytes contain the IO-Link port qualifier information bytes for port 0 … 3.
3) Factory setting
Tab. 10
The "IO-Link Device Tool" software can be used to set the address space (data length inputs/outputs)
è
The setting is saved permanently in the module. Changes only become effective after a restart of the
automation system CPX-AP.
8.2
IO-Link Device description file (IO-Link Device Description)
IO-Link Device information can be imported into the module via an IO-Link device description file.
The "Festo IO-Link Tool" software can be used to import the IO-Link device description file
è
9
Parameterisation
Various parameters are available for reading out information about the modules in an automation sys-
tem CPX-AP and adapting the modules to the application situation.
Parameterisation
10
Festo — CPX-AP-I-4IOL-M12 — 2020-03